Page 48 - policy and procedure infection control
P. 48

Policies and Procedures on Infection Control




                  3.5     Design of Isolation Rooms





                Patients who need airborne isolation should be placed in well ventilated areas with a directional
                airflow from health care worker to the patient. Adequate ventilation is commonly defined by air
                exchange rate.  It is desirable to achieve > 12 air change rates per hour (ACH). The air should
                flow from corridors (cleaner areas) into isolation rooms (less clean areas) to prevent spread of
                contaminants to other areas.

                3.5.1 Ventilation
                      This can be achieved by three possible strategies,
                      1.  Natural ventilation
                          This may be an option provided the isolation areas are away from other parts of the
                          hospital, and are built in places predicted to have good prevailing winds year round.

                          The air should be directed from patient caring areas to outside open areas not regularly
                          used for transit of persons.
                          Inside the airborne precaution room, the patient should be placed near the exterior
                          wall, close to open window(s), instead of close to the inner wall.
                      2.  Use of exhaust fans
                          In places where natural ventilation is not suitable, and fully mechanically-ventilated
                          airborne precaution rooms cannot be installed due to limited resources, the use of
                          exhaust fans (with adequate pre-testing and planning) may help to increase ACH
                          rates and generate negative pressure in the rooms.
                          The fans should be installed on exterior wall(s) where room air can be exhausted
                          directly to the outdoor environment free of transit of persons.
                          The size and number of exhaust fans needed depend on the targeted ACH, which
                          must be measured and tested before use. The position of exhaust fans with relation
                          to doors and windows should be carefully planned to avoid short circuiting.
                      3.  Use of mechanical ventilation
                          The engineering requirements for a mechanically ventilated negative pressure rooms
                          are as follows,
                          •  Negative pressure (greater exhaust than supply air volume);

                          •  Pressure differential of 2.5 Pa (0.01-in. water gauge);
                          •  Air flow volume differential >125-cfm exhaust versus supply;
                          •  Well sealed room, approximately 0.5-sq. ft. leakage;






                                                                          Ministry of Health Malaysia  37
   43   44   45   46   47   48   49   50   51   52   53