Page 17 - Advanced Course
P. 17

KNX ADVANCED COURSE

                  Some specific features should be noted when using read flags:
                      If read flags are used in an installation (e.g. when storing light scenes), it should be
                      ensured that the read flag is only set once for each group address in order to avoid
                      multiple responses after a read request.
                      The read flag should only be set at the bus device which is to respond.
                      The group address that is used to read out the object status must be placed at the
                      transmission point of the bus device that should be read out since the response
                      telegram uses this group address.









































































                  Home and Building Management Systems                                    KNX Association
                  Flags                                  Flags_E1212b.doc                             6/13