KNX ADVANCED COURSE

                  A short circuit or disruption of the external set zone leads to a sabotage alarm.











                  Figure 29: Set zone


                  3.7.5  Panic Zone

                  Panic zones are primary circuits with an EOL resistor of 2.7 kΩ.













                  Figure 30: Panic zone


                  The disruption of a panic zone always leads to the triggering of a remote alarm.



                  3.7.6  External Local Alarm Signal

                  The supply cables to the signalling devices are not monitored for intruder alarm control
                  units. A short circuit or disruption of these cables is not detected.












                  Figure 31: External local alarm signal

                  A further option is to set up the supply cable to the external signalling devices as a
                  primary cable which is monitored for a short circuit or disruption.
                  The alarm circuits to the external signalling devices are each provided with an EOL
                  resistor of 1 kΩ. A short circuit or disruption of the alarm circuits leads to a sabotage
                  alarm.