Page 39 - Serial Data Transmission and KNX Protocol
P. 39

KNX TUTOR SEMINAR

























                  Figure 6: Ctrl-Mode

                  6.2.2  PB-Mode

                  In PB-Mode, the configuration starts with taking Individual Addresses. Every separate
                                                                                         rd
                  device searches for itself a free Individual Address. Even further on, no 3  party - like
                  ETS or a central controller - is needed. Instead, the PB-Mode themselves configure each
                  other. The installer firstly selects an actuator Channel (typically by pressing a push button
                  on it) and then a sensor E-Mode Channel. The underneath figure sketches how these two
                  Channels (devices) then negotiate whether or not a link shall be established, and the
                  parameters and Group Addresses to be used for this. The installer can repeat the
                  procedure for this or another actuator Channel and other sensor Channels, always two by
                  two. The devices do not write each other’s Address Table or parameter memory. Instead,
                  PB-Mode device have some dedicated services and commands to do this without
                  knowing the mask and memory map of the communication partner.



















                  Figure 7: PB-Mode














                  Home and Building Management Systems                                   KNX Association
                  Serial Data Transmission and KNX Protocol     Serial Data Transmission_E0808f.doc   39/41
   34   35   36   37   38   39   40   41