Page 21 - Avenger Submittal reduced
P. 21

AS2010-00


       Fixed Temp / Rate of Rise Heat Detector





                                               Standard Features                    Operation

                                               •   Low Profile - Only 2.0” high, including   The AS2010 incorporates a highly linear
                                                  base                              thermistor circuit.  The specially  designed
                                                                                    cover protects the thermistor while allowing
                                               •   Simple and reliable device addressing   maximum air flow. The thermistor  circuit
                                                  method                            produces a voltage proportional to the
                                                                                    temperature; this information is transmitted
                                               •   Uses the noise Immune Digital    to the control panel as a digital value. When
                                                  Communication Protocol (DCP),     the ambient temperature exceeds a
                                                  which utilizes interrupts for fast   preprogrammed threshold (fixed temp or
                                                  response to fires.                rate of rise), the sensor transmits an interrupt
                                               •   Rate of Rise temperature threshold =   to the control panel indicating a fire alarm.
                                                  15°F/Min (determined by panel)    The fire alarm control panel can adjust the
                                                                                    sensor’s fixed temperature threshold for
                                               •   Adjustable threshold temperature=   different installation requirements.
                                                  135°F -190°F (determined by panel)
                                                                                    Up to 127 devices may be installed on each
                                               Application                          SLC loop. The sensor address may be set by a
                                                                                    hand-held programming unit. The sensor
                                                                                    mounts to an electronics-free base and
                                               The AS2010 Fixed Temperature /  Rate of   incorporates a locking mechanism for
                                               Rise sensors provide accurate temperature   security. The base provides mounting slots,
                                               measurement data to the fire alarm control   terminals for field wiring and a third terminal
                                               panel. These sensors are well-suited for   for a remote indicator/ LED. The sensor has
                                               environments where dust, cooking fumes   dual LEDs for  easy viewing of the sensor
                                               or other factors make the use of smoke   status.
                                               sensors Impractical.








         Note:

         Bases are not included

         with detectors, please

         order separately.












                    Fire Detection System by Avenger, Las Vegas, Nevada 89141 U.S.A. I Phone: 1-702-513-4654
                                     info@avengersystems.com I www.avengersystems.com
                                                                                                    VERSION 3.01 - 2017/09