KNX ADVANCED COURSE




                                Dimming value X%
                                Dimmer UP                Dimming
                                Dimmer DOWN

                                  OFF command
                                  Dimming value OFF
                                                          STOP
                                                          Value reached
                                                          ON command
                                                                              Dimming value X%
                                                                              Dimmer UP
                        Dimming value OFF                                     Dimmer DOWN
                        OFF command              Dimmer UP
                        Dimmer DOWN              Dimming value X%                     ON command
                        STOP                                                         STOP
                                                         ON command
                                       OFF                                        ON
                                                         OFF command
                                                         Dimming value OFF





                  5.3  Functional Block – Sunblind Actuator Basic


                  5.3.1  General

                  The function “Drive Control” is used primarily for controlling blind and roller shutter
                  motors.
                  A sunblind actuator shall per channel at least support two group objects complying to the
                  underneath stated DPTs:

                      StopStep UpDown, DPT 1.007
                      Move UpDown, DPT 1.008
                  Any other group objects are optional.
                  Important: Group objects using this function shall not reply to read requests through the
                  bus (Group Value Read messages). This restriction ensures that drives are not
                  inadvertently set into motion. The READ flag of the group objects shall therefore be reset!
                  This applies both to sensors AND actuators!
                  If devices are not of the type BCU1, the above is not needed, provided the update flag in
                  the respective objects are not set.