Page 28 - Serial Data Transmission and KNX Protocol
P. 28

KNX TUTOR SEMINAR

                  4  Different APCI Codings


                  4.1  General

                  The task of the application layer is to manage the values of the group objects on behalf of
                  the application program, process group telegrams as well as carry out management
                  functions.
                  In run-time communication (i.e. after configuration), the typical APCIs used are:


                             APCI            Name

                             0000            GroupValueRead
                             0001            GroupValueResponse

                             0010            GroupValueWrite

                  These APCIs are used in conjunction in multicast communication, i.e. the target
                  addresses of these telegrams are group addresses, useful data is coded according to the
                  KNX Interworking Data types.

                  Configuration of bus devices is ensured via management functions, which are typically
                  stored in the ROM of the bus device. For such management functions, typically
                  connection-oriented (point-to-point) communication or broadcast (group address 0/0) is
                  used.

                  Very commonly used APCIs are:


                             APCI                          Name
                             0011            IndividualAddrWrite

                             0100            IndividualAddrRequest
                             0101            IndividualAddrResponse

                             0110            AdcRead
                             0111            AdcResponse

                             1000            MemoryRead
                             1001            MemoryResponse

                             1010            MemoryWrite
                             1011            UserMessage

                             1100            MaskVersionRead
                             1101            MaskVersionResponse

                             1110            Restart
                             1111            Escape



                  Home and Building Management Systems                                   KNX Association
                  Serial Data Transmission and KNX Protocol     Serial Data Transmission_E0808f.doc   28/41
   23   24   25   26   27   28   29   30   31   32   33