Page 31 - Serial Data Transmission and KNX Protocol
P. 31
KNX TUTOR SEMINAR
IndividualAddressResponse
Response to an IndividualAddressRequest of all those bus devices of a KNX installation
that are currently in the programming mode (their programming LED lights up). The target
address in the telegram is 0/0 (broadcast).
01 01 Xxxxxx
4
x...x: no significance
AdcRead
Requests the addressed bus device to carry out a number of A to D conversions,
calculate the sum and return the result, of the indicated A to D channel.
01 10 Aaaaaaa cccccccc
a...a: number of the A to D channel to be read
c...c: number of A to D conversions to be carried out and summed
AdcResponse
Response to AdcRead containing the requested data.
01 11 aaaaaa cccccccc hhhhhhhh LLLLLLLL
a...a: number of the A to D channel read
c...c: number of A to D conversions carried out and summed
h...h: high byte of the result
L...L: low byte of the result
MemoryRead
Requests the addressed bus device to transmit its memory contents, starting at the
specified address.
10 00 XXLLLL aaaaaaaa bbbbbbbb
L...L: length of the memory area to be read (bytes)
a...a: starting address of the memory area to be read (high byte)
b...b: starting address of the memory area to be read (low byte)
Home and Building Management Systems KNX Association
Serial Data Transmission and KNX Protocol Serial Data Transmission_E0808f.doc 31/41