Page 203 - 3rd issue
P. 203
intelligent
0.6/1 (1.2) kV
Multicore Cables, with Stranded
Aluminum Conductors XLPE
Insulated and PVC Sheathed Binder tape
XLPE insulation PVC Sheathing
Description Aluminum Conductor
• Multicore cables of stranded Aluminium conductors are insulated with XLPE compound, assembled together
and covered with an overall jacket of PVC compound.
• Cables are produced according to IEC 60502.
Application
• For outdoor and indoor installations in damp and wet locations. They are normally used for power
distribution in urban networks, in industrial plants, as well as in thermopower and hydropower stations.
Nominal Cross Max. Conductor Resistance Current Rating Approx.
Sectional Area Laid in Ducts Overall
Product-Code DC at AC at Laid direct in Laid in Free Air Diameter Approx Weight
mm2 20 OC 90 OC Ground A A kg / km
Ω/km Ω/km A mm
Two Core Cables
A14X202UP 10 rm 3.0800 3.9500 57 48 55 13.8 235
A15X202UP
A16X202UP 16 rm 1.9100 2.4500 74 58 73 15.8 310
A17X202UP
25 rm 1.2000 1.5400 97 75 97 18.8 450
35 rm 0.8680 1.1130 128 106 120 21.0 565
Three Core Cables
A14X203UP 10 rm 3.0800 3.9500 52 42 48 15.1 250
A15X203UP
A16X203UP 16 rm 1.9100 2.4500 68 52 62 17.3 330
A17X203UP
25 rm 1.2000 1.5400 90 71 84 20.5 460
35 rm 0.8680 1.1130 120 95 105 22.9 580
Four Core Cables
A14X204UP 10 rm 3.0800 3.9500 52 42 48 16.4 320
A15X204UP
A16X204UP 16 rm 1.9100 2.4500 68 52 62 18.9 405
A17X204UP
A18X204UP 25 sm 1.2000 1.5400 90 71 84 22.5 585
A19X204UP
A20X204UP 35 sm 0.8680 1.1130 120 95 110 25.2 745
A21X204UP
A22X204UP 50 sm 0.6410 0.8220 145 110 136 26.5 905
A23X204UP
A24X204UP 70 sm 0.4430 0.5690 175 140 168 30.8 1260
A25X204UP
95 sm 0.3200 0.4110 210 165 205 33.5 1565
120 sm 0.2530 0.3250 235 190 236 37.6 1950
150 sm 0.2060 0.2650 265 215 278 42.1 2405
185 sm 0.1640 0.2120 290 240 315 47.1 2930
240 sm 0.1250 0.1630 340 280 378 52.9 3725
300 sm 0.1000 0.1310 390 325 446 58.5 4625
Nominal Cross Max. Conductor Resistance Current Rating Approx. Approx
Sectional Area Overall Weight
Product-Code DC at AC at Laid direct in Laid in Ducts Laid in Free Air Diameter
mm2 20 OC 90 OC Ground A kg / km
A17X2R3UP Ω/km Ω/km A A mm
A18X2R3UP
A19X2R3UP Four Core Cables with Reduced Neutral 95
A20X2R3UP 110
A21X2R3UP 35 sm 16 rm 0.8680/1.9100 1.1130/2.4500 120 140 110 23.6 670
A22X2R3UP 50 sm 25 sm 0.6410/1.2000 0.8220/1.5400 145 165 136 25.3 830
A23X2R3UP 70 sm 35 sm 0.4430/0.8680 0.5690/1.1130 175 190 168 29.1 1120
A24X2R3UP 95 sm 50 sm 0.3200/0.6410 0.4110/0.8220 210 215 205 33.0 1415
A25X2R3UP 120 sm 70 sm 0.2530/0.4430 0.3250/0.5690 235 240 236 35.9 1770
150 sm 70 sm 0.2060/0.4430 0.2650/0.5690 265 280 278 39.7 2120
185 sm 95 sm 0.1640/0.3200 0.2120/0.4110 290 325 315 44.6 2590
240 sm 120 sm 0.1250/0.2530 0.1630/0.3250 340 378 49.9 3260
300 sm 150 sm 0.1000/0.2060 0.1310/0.2650 390 446 55.2 4065
The data is approximate an subjected to manufacturing tolerance. rm: round stranded
sm: sector stranded
We own the power