0.6/1 (1.2) kV
Multicore Cables, with Stranded
Aluminum Conductors XLPE
Insulated and PVC Sheathed Aluminum conductor Inner Sheathing
Description XLPE insulation tape STA PVC Sheathing
Binder ( Steel tape Armoring
)
• Multicore cables of stranded Aluminium conductors are insulated with XLPE compound,, assembled
together, armoured with steel tape and covered with an overall jacket of PVC compound.
• Cables are produced according to IEC 60502.
Application
• For outdoor Installation in damp wet locations where mechanical damages are expected to occur.
Nominal Cross Max. Conductor Resistance Current Rating Approx. Approx
Sectional Area Laid in Ducts Overall Weight
Product-Code DC at AC at Laid direct in Laid in Free Diameter
mm2 20 OC 90 OC Ground A Air kg / km
A14X202IP A A mm
A15X202IP Ω/km Ω/km
A16X202IP
A17X202IP Two Core Cables
A14X203IP 10 rm 3.0800 3.9500 56 47 55 15.8 370
A15X203IP
A16X203IP 16 rm 1.9100 2.4500 73 57 72 17.8 460
A17X203IP
25 rm 1.2000 1.5400 96 74 96 20.8 630
A14X204IP
A15X204IP 35 rm 0.8680 1.1130 129 105 126 23.0 770
A16X204IP
A17X204IP Three Core Cables
A18X204IP
A19X204IP 10 rm 3.0800 3.9500 52 41 47 17.1 390
A20X204IP
A21X204IP 16 rm 1.9100 2.4500 67 52 62 19.3 495
A22X204IP
A23X204IP 25 rm 1.2000 1.5400 89 70 84 22.5 650
A24X204IP
A25X204IP 35 rm 0.8680 1.1130 120 95 110 24.9 795
Product-Code Four Core Cables
A17X2R3IP 10 rm 3.0800 3.9500 52 41 47 18.4 475
A18X2R3IP
A19X2R3IP 16 rm 1.9100 2.4500 67 52 62 20.9 585
A20X2R3IP
A21X2R3IP 25 sm 1.2000 1.5400 89 70 84 24.5 780
A22X2R3IP
A23X2R3IP 35 sm 0.8680 1.1130 120 95 110 27.2 940
A24X2R3IP
A25X2R3IP 50 sm 0.6410 0.8220 145 110 136 30.1 1300
70 sm 0.4430 0.5690 175 140 168 34.6 1750
95 sm 0.3200 0.4110 210 165 205 39.7 2540
120 sm 0.2520 0.3250 235 190 236 43.8 3020
150 sm 0.2060 0.2650 265 215 278 48.7 3670
185 sm 0.1640 0.2120 290 240 315 53.7 4380
240 sm 0.1250 0.1630 340 280 378 60.0 4430
300 sm 0.1000 0.1310 390 325 446 65.5 6510
Nominal Cross Max. Conductor Resistance Current Rating Approx. Approx
Sectional Area Laid in Ducts Overall Weight
DC at AC at Laid direct in Laid in Free Diameter
mm2 20 OC 90 OC Ground A Air kg / km
A A mm
Ω/km Ω/km
Four Core Cables with Reduced Neutral
35 sm 16 rm 0.8680/1.9100 1.1130/2.4500 120 95 110 25.6 890
50 sm 25 sm
70 sm 35 sm 0.6410/1.2000 0.8220/1.5400 145 110 136 28.7 1200
95 sm 50 sm
120 sm 70 sm 0.4430/0.8680 0.5690/1.1130 175 140 168 33.1 1550
150 sm 70 sm
185 sm 95 sm 0.3200/0.6410 0.4110/0.8220 210 165 205 38.0 1970
240 sm 120 sm
300 sm 150 sm 0.2530/0.4430 0.3250/0.5690 235 190 236 42.1 2710
0.2060/0.4430 0.2650/0.5690 265 215 278 46.3 3290
0.1640/0.3200 0.2120/0.4110 290 240 315 51.2 3980
0.1250/0.2530 0.1630/0.3250 340 280 378 57.1 4910
0.1000/0.2060 0.1310/0.2650 390 325 446 62.2 5920
The data is approximate an subjected to manufacturing tolerance. rm: round stranded
sm: sector stranded
We own the power