Page 336 - 3rd issue
P. 336
intelligent
Phase Max. DC, Approx. Overall
resistance at Diameter
Copper Conductors & Product – Code Nominal cross Insulation Approx. Weight
XLPE +2.5 % C.B sectional area thickness 20oC kn
mm
mm2 mm / km
198
Two conductors (Duplex) 307
469
XLPE Insulation Copper conductor H014W202 10 1.2 1.830 10.7 650
H015W202 16 1.2 1.150 12.8 898
Description H016W202 25 1.2 0.727 15.3 1247
H017W202 35 1.2 0.524 17.6 1736
• They are composed of one or H018W202 50 1.5 0.387 21.2 2170
more insulated conductors and H019W202 70 1.5 0.268 24.5
one neutral (bare or insulated) H020W202 95 1.5 0.193 28.3 305
conductor. They are required as H021W202 120 1.7 0.153 31.8 471
two (Duplex) or three (Triplex) or 719
four (Quadru-plex) conductors, H014W203 Three conductors (Triplex) 991
XLPE with 2.5% Carbon black H015W203 1357
insulated. H016W203 10 1.2 1.830 13.7 1900
• As per NEMA WC 7/IEC60228 H017W203 16 1.2 1.150 15.8 2631
H018W203 25 1.2 0.727 18.5 3285
Application H019W203 35 1.2 0.524 20.7
H020W203 50 1.5 0.387 25.0 413
•They are used for secondary over H021W203 70 1.5 0.268 28.7 634
95 1.5 0.193 32.4 970
head lines (in circuits not exceeding H014W204 120 1.7 0.153 36.6 1332
H015W204 1821
1000 volts phase to phase) on H016W204 Four conductors (Quadruplex) 2553
H017W204 3526
poles or as feeders to residential H018W204 10 1.2 1.830 16.3 4579
H019W204 16 1.2 1.150 18.8
premises H020W204 25 1.2 0.727 22.0
H021W204 35 1.2 0.524 24.6
Copper conductors with bare neutral 50 1.5 0.387 29.8
adopted from IEC 60228. 70 1.5 0.268 34.2
95 1.5 0.193 38.6
120 1.7 0.153 43.5
The data is approximate an subjected to manufacturing tolerance.
Phase Max. DC, Aluminum Conductors
resistance at Approx. Weight & XLPE +2.5 % C.B
Product – Code Nominal Insulation Approx. Overall
cross thickness 20oC Diameter mm
B015W202
B016W202 sectional area mm / km kn
B017W202 mm2
B018W202 12.9
B019W202 Two conductors (Duplex) 15.3 Aluminum conductor XLPE Insulation
B020W202 17.7
B021W202 16 1.2 1.910 21.4 115
24.4
B015W203 25 1.2 1.200 28.4 168
B016W203 31.8
B017W203 35 1.2 0.868 229 Description
B018W203 50 1.5 0.641 15.6
B019W203 70 1.5 0.443 18.0 322
B020W203 95 1.5 0.320 20.4 428
B021W203 120 1.7 0.253 25.2 626 • They are composed of one or
28.2 734 more insulated conductors and
B015W204 Three conductors (Triplex) 32.2
B016W204 36.6 one neutral (bare or insulated)
B017W204 16 1.2 1.910 185 conductor. They are required as
B018W204 25 1.2 1.200 19.0 267 two (Duplex) or three (Triplex) or
B019W204 35 1.2 0.868 22.0 364
B020W204 50 1.5 0.641 24.9 519 four (Quadru-plex) conductors,
B021W204 70 1.5 0.443 30.3 674 XLPE with 2.5% Carbon black
95 1.5 0.320 33.9 928 insulated.
120 1.7 0.253 38.8
43.5 1245 • As per NEMA WC 7/IEC6022
Four conductors (Quadruplex) Application
16 1.2 1.910 256 • They are used for secondary
25 1.2 1.200 367 over head lines (in circuits not
35 1.2 0.868
499 exceeding 1000 volts phase to
50 1.5 0.641 710 phase) on poles or as feeders to
70 1.5 0.443 920
95 1.5 0.320 1263 residential premises.
120 1.7 0.253
1556 Copper conductors with bare neutral
adopted from IEC 60228.
The data is approximate an subjected to manufacturing tolerance.