Page 105 - belden
P. 105
I N DUS T R I A L A U T O M A TI O N & P R O C E S S C O NTRO L C A B L E S 105
UL/CSA Control Cable
®
600V Teck-style Cables: Dual-Rated Type MC/TECK 90
Interlocked Armor • Industrial Cable
Composite Cables • UL MC
• CSA C22.2 No.131 FT4 Flame Test, HAZ LOC
• CSA C22.2 No. 0.3 Clause 4.31 Low Acid Gas
• Direct Burial
Pull Tension Bend Radius Insulation
Part No. Color Inner Jacket OD Armor OD OD (Nom)
Conductors (Max) (Min) Thickness
Code
Aluminum Steel Inch mm Inch mm Inch mm Lbs N Inch mm Inch mm
Stranded (7 x 22 and 7 x 20) BC Conductors • XLP Insulation • PVC Inner Jacket • Interlocked Armor • PVC Outer Jacket
14 AWG and 12 AWG • 12 AWG Uninsulated Ground Wire
27890 28890 3 + 3 Note 1: .56 14.22 .75 19.05 .86 21.84 202 899 10.3 262 .030 .76
Stranded (7 x 22 and 7 x 18) BC Conductors • XLP Insulation • PVC Inner Jacket • Interlocked Armor • PVC Outer Jacket
14 AWG and 10 AWG • 10 AWG Uninsulated Ground Wire
27891 28891 3 + 3 Note 1: .61 15.49 .80 20.32 .91 23.11 305 1357 10.9 277 .030 .76
Stranded (7 x 22 and 7 x 16) BC Conductors • XLP Insulation • PVC Inner Jacket • Interlocked Armor • PVC Outer Jacket
14 AWG and 8 AWG • 10 AWG Uninsulated Ground Wire
.030 (14 AWG) 0.76
27892 28892 3 + 3 Note 1: .70 17.78 .96 24.38 1.07 27.18 435 1935 12.8 325
.045 (8 AWG) 1.14
Stranded (7 x 22 and 7 x 14) BC Conductors • XLP Insulation • PVC Inner Jacket • Interlocked Armor • PVC Outer Jacket
14 AWG and 6 AWG • 6 AWG Uninsulated Ground Wire
.030 (14 AWG) 0.76
27893 28893 3 + 3 Note 1: .90 22.86 1.15 29.21 1.26 32.00 655 2914 15.1 384
.060 (6 AWG) 1.52
Note 1: 14, 12, and 10 AWG use ICEA Table E2 with printed numbers. 8 AWG and larger, use ICEA M4 with printed numbers.
BC = Bare Copper • PVC = Polyvinyl Chloride • XLP = Cross-Linked Poly