XHHW


              9 0  º  D   C  7 /   y r  5    C º  W  t e  6 0 0  V    s t l o                 U   4   L  4



               Specification : UL44










                                XHHW  #  40/  AWG  600 V   MESC  2005



             Application: Widely used for Control, Switch Boards, Lighting and Power Circuits in residential and
                           commercial buildings.  Also used for industrial plants and utility substations.



              Construction


               Conductor     :   Plain copper to ASTM B 3 stranded to class B of ASTM B 8.


               Insulation     :  XLPE as per ICEA  S -66 -524.  UL Type XHHW conductors.  Any required
                                 colour can be provided.


                Order         MESC CODE           Size      Strand X  Insulation  Approx.  Approx.
                                                             Dia.     Thickness  O. D.    Weight  Ampacity *
                 No.                            AWG/MCM    No. X mm     mm        mm      Kg/Km.
                66001   6614 -01C14AWG-U0BK1 -00    14      7X0.615     0.76       3.4      26        25 **
                66002   6614- 01C12AWG-U0BK1 -00    12      7X0.775      0.76      3.9      38        30  **
                66003   6614 -01C10AWG-U0BK1 -00    10      7X0.978     0.76       4.5      58        40  **
                66004   6614 -01C08AWG-U0BK1 -00     8      7X1.23      1.14       6.1      95        55
                66005   6614 -01C06AWG-U0BK1 -00     6      7X1.56      1.14       7.1     146        75
                66006   6614 -01C04AWG-U0BK1 -00     4      7X1.96      1.14       8.3     222        95
                66007   6614 -01C02AWG-U0BK1 -00     2      7X2.47      1.14       9.8     343       130
                66008   6614- 01C01AWG-U0BK8 -00     1     19X1.69       1.40     11.4     438       150
                66009   6614 -01C10/AW-U0BK8 -00     1 /0   19X1.89      1.40      12.4     541      170
                66010   6614 -01C20/AW-U0BK8 -00     2 /0   19X2.13      1.40      13.6     679      195
                66011   6614 -01C40/AW-U0BK8 -00     4 /0   19X2.68      1.40      16.3    1056      260
                66012   6614 -01C250MC-U0BK8 -0       250   37X2.09      1.65      18.1    1253       290
                66013   6614 -01C300MC-U0BK8 -00     300    37X2.29      1.65      19.5    1495       320


                   *  Based on not more than three conductors in raceway or cable or earth (Directly Buried)
                   *  Unless otherwise specifically permitted in the NEC, the  overcurrent protection for conductor shall not
                      exceed 15 ampere for 14 AWG, 20  ampere  for 12  AWG  and 30 ampere for 10 AWG after
                      correction factors for  ambient  temperature  and number  of  conductors have been applied.


              Packing: Upto 2 AWG shrinked wrapped coils of 100  yards.  For 1 AWG and above wooden drums of
                      500/ 1000 meter.
                      For colours other than Black, please replace BK in the code by "BL"   for Blue, "BN" for brown, "GN"
                      for Green, "GY" for Grey, "OR" for Orange, "PK" for Pink, "RD" for Red,"TR" for Turquoise, "VT" for