74 - No-Break KS® Mechanical / Electrical Features
System Construction Configurations
The external appearance of EURO-DIESEL’s No-Break KS® resembles Single Stand-Alone Unit
that of a conventional generating set. For simple low component count reliability.
However, it consists of a diesel engine coupled by means of an
electromagnetic clutch to a stato-alternator, which is the combination of Dual Output
a synchronous machine and a kinetic energy accumulator. A dual output design can be configured to provide site critical and
The No-Break KS® system also involves a choke and 3 circuit breakers. non-critical loads, removing the requirement for gensets. There are
variations of this design to suit isolated or non-isolated schemes.
Control Panel Touchscreen Power Panel
HMI KS-VISION® (Switchgear & Choke) Parallel Redundant N or N+1
Parallel LV or MV solutions can be configured to allow redundancy and
Diesel Engine Kinetic Energy capacity, expansion and modularity.
Electromagnetic Clutch Accumulator Dual Bus N or N+1
In higher tier requirements and to remove the single point of failure in a
Synchronous Machine Tier II solution, a double busbar design can be provided. This allows for
isolation and maintenance of individual machines and output switchgear
Operating Modes sections. LV or MV alternators are available.
Normal Mode 2N or 2N+1 High Availability
In normal mode, when the mains is within tolerance, the synchronous Two totally separate parallel redundant systems can be configured to
machine is acting as a synchronous motor, driving the kinetic energy meet Tier IV and 2N or 2N+1 requirements. The output busbars are
accumulator and storing kinetic energy within it. synchronised allowing seamless load transfers.
Emergency Mode Isolated Parallel
Since 1999 EURO-DIESEL has been supplying Isolated Parallel (IP)
In emergency mode, on mains failure or out of tolerance mains events, solutions. This arrangement enables multiple LV systems to be paralleled
the QD1 breaker opens and the stored kinetic energy is retrieved and with an interposing choke limiting the short circuit of the output. This
transferred to the synchronous machine, which is now acting as a removes the need to have special output switchboards. EURO-DIESEL
generator. This occurs without any interruption to the downstream load. has developed both IP Ring and IP Star configurations allowing for multi
Shortly after mains failure, the diesel engine is started and coupled to MW installations meeting Tier III and Tier IV requirements.
the synchronous machine by closing the electromagnetic clutch.
The energy is then provided to the synchronous generator by the diesel EURO-DIESEL’s IP system provides significant advantages over
engine for an unlimited period. conventional configurations: higher loaded units at all times; higher overall
efficiency; improved fault tolerance; simple load sharing; reduction in the
number of modules; isolation between units and simple maintainability. The
KS-VISION® control system is configured to match this solution without the
need for a master controller and therefore removing single points of failure.
No-Break KS® IP Star-Bus Configuration
No-Break KS® Conditioning Mode
No-Break KS® IP Ring-Bus Configuration