Page 83 - E24 Electrical Notebook
P. 83
UPS Application Design Guidance - 79
Static UPS 380 - 415 V 50 Hz Output 380 - 415 V 50 Hz
± 15%
Technical Data - AP Premium > 0.99 Voltage: ± 1% Steady State
Input Voltage Tolerance:
< 3% Frequency Tolerance: ± 1%
Voltage: Up to 2,000% for 100ms
Voltage Tolerance: Overload Capacity: (Switching to Bypass)
Power Factor at rated Voltage: Up to 188% for 10mins
THDi (Normal Op.): Up to 96.0%
General Efficiency:
Operational Altitude: Up to 1000m ASL
Ambient Temperature: 0 - 40 °C Daily Average ≤ 35°C
Relative Humidity: 5 - 95% Non-Condensing
Ingress Protection: IP 20
Static UPS Guide to Dimensions & Weights
100 kVA 120 kVA 160 kVA 200 kVA 300 kVA 400 kVA 500 kVA
LxWxH LxWxH LxWxH LxWxH Lx W x H LxWxH LxWxH
Static UPS 800 x 800 x 1900 800 x 800 x 1900 1200 x 800 x 1900 1200 x 800 x 1900 1600 x 800 x 1900 2000 x 800 x 1900 2000 x 800 x 1900
Weight kg
600 660 895 895 1335 1715 1715
5 mins Batt. on
Stand 1080 x 630 x 1195 1080 x 630 x 1195 900 x 800 x 1315 1430 x 630 x 1590 1595 x 800 x 1600 1610 x 800 x 2390 2970 x 830 x 1249
Weight kg
914 971 1575 1715 2516 3450 3850
10 mins Batt. on
Stand 1070 x 800 x 1205 900 x 800 x 1315 1430 x 800 x 1600 1595 x 800 x 1600 1595 x 800 x 2390 3005 x 800 x 1600 2970 x 830 x 1649
Weight kg
1260 1575 2096 1516 3775 5035 5300
Static Transfer Switch
Technical Data - APOTRANS Design Type Fuse-less
Input 380-415V Transfer Times: <2ms Manual; <3ms Automatic:
50 Hz ± 5% Short Circuit Current: Up to 50kA
Rated Voltage: Overall Locus Diagram Noise Level: <65 dB(A)
Rated Frequency: 120% - 10 min, 1505 - 2 min Operational Altitude: Up to 1000m ASL
Power Factor: >5 Relative Humidity: 20 to 90% Non Condensing
Overload: >99.0% Ingress Protection: IP 20 (Standard Enclosure)
Crest Factor:
Efficiency:
Piller APOTRANS Static Transfer Switch Guide to Dimensions & Weights
Standard Enclosure with Service Bypass Chassis Unit for Integration into Switchboard / PDU
APOTRANS Width (mm) Depth (mm) Height (mm) Weight (kg) APOTRANS Width (mm) Depth (mm) Height (mm) Weight (kg)
25A - 63A 500 436 557 34 100A 560 527 1120 120
100A 800 800 1900 309
160A 800 800 1900 309 160A 560 527 1120 120
250A 800 800 1900 333
400A 1200 800 1900 572 250A 560 527 1120 144
630A 1200 800 1900 572
800A 1600 800 1900 767 400A 618 527 1620 240
1000A 1600 800 1900 767
1600A 2400 823 2158 1300 630A 618 527 1620 240
800A 618 527 1620 272
1000A 618 527 1620 272
Piller UK Ltd Tel : 01285 657721
Westgate Fax : 01285 654823
Phoenix Way
Cirencester Email : uk@piller.com
Glos GL7 1RY Website : www.piller.com