Havells Metering & Surge Protection - 91
Metering Requirements
Part L2 of the building regulations has fundamentally changed how electrical systems for buildings
are designed and installed.
• At least 90% of energy consumption in buildings larger than 500m² must be accounted for
• An energy performance certificate demonstrating compliance is required for every building
• Automatic meter reading (AMR) in all new buildings over 1000m² must be incorporated
• Additional metering would be required for plant items with input powers greater than or equal
to those shown below
Plant Item Rated Input Metered 125A Type B Distribution Board
Power (kW) Tri-Load Meter
Boiler installations comprising one or more boilers or CHP plant feeding a MID Approved Meter Unit
common distribution circuit 50 Surge Protection Device for Type B Distribution Board
Chiller installations comprising one or more chiller units feeding a common 20
distribution circuit
Electric humidifiers 10
Motor control centres providing power to fans and pumps 10
Final electrical distribution boards 50
Havells offers a comprehensive solution to metering and measuring energy consumption in
buildings. The key for Havells is our understanding of regulations, future requirements for metering
and what it means to the installer.
The range of metering solutions includes both integrated and retro fit with features such as ease
of install, pre-configuration (reducing risk of errors) and MID options, making the installers life
easy when considering metering.
What is MID?
The Measuring Instruments Directive (MID) was introduced by the European Commission to
promote free trade of measuring instruments throughout Europe.
Any meter used for billing of electricity, must be either MID approved or approved under UK
national legislation. Meters already installed, that were approved under UK national legislation
prior to October 2006 may remain installed indefinitely, as long as they are measuring accurately.
Any new meter manufactured and approved after October 2006 must be approved under the MID
regulations.
In the UK, the MID is applicable for loads up to 100kW. After October 2016 every new meter
installed for billing must be MID approved. It is a criminal offence to use a non-approved meter
for billing.
Surge Protection: Havells & Furse
Furse is a world leader in the design, manufacture and supply of earthing and lightning protection
systems.
A Havells/Furse strategic alliance offers fully type tested solutions of complete assemblies,
including Type A/B distribution boards and MCCB panel boards.
This concept is unique to the current selection of surge protection devices within an electrical
system as a proven level of energy let through voltage can be confirmed for a complete assembly
and not simply sub components.
The configuration of surge protection devices within each assembly has been standardised to
reduce installation variables to ensure that a surge protection device operates at optimum
performance maintaining the integrity of the electrical system.
• Fully type tested solutions validated by Furse
• Standardised kits to reduce installation variables for optimum performance
• Compliance to BS EN62305 & IET Wiring Regulations BS 7671:2008 (+A1:2011)