KNX BASIC COURSE
Primary protection is achieved by using:
For the 230/400 V AC mains:
nominal discharge current at least 12,5 kA (10/350 µs) per conductor
protection level: < 4 kV
Surge protection device (SPD) Type 1 according EN 61643-11:2001
For the bus line
nominal discharge current at least 2,5 kA (10/350 µs) per conductor
protection level: < 600 V
Surge protection device (SPD) Category D1 according 61643-21:2002
Home and Building Management Systems KNX Association
KNX TP Installation Installation_E1213c 18/28