                  Primary protection is achieved by using:

                      For the 230/400 V AC mains:
                        nominal discharge current at least 12,5 kA (10/350 µs) per conductor
                        protection level: < 4 kV
                        Surge protection device (SPD) Type 1 according EN 61643-11:2001
                      For the bus line

                        nominal discharge current at least 2,5 kA (10/350 µs) per conductor
                        protection level: < 600 V
                        Surge protection device (SPD) Category D1 according 61643-21:2002