High Voltage Cables
38/66 (72.5) kV
(CU/XLPE/LEAD/HDPE)

           Description.

           Stranded circular compacted or segmental conductor with copper or Aluminum material,
           Semi-Conducting layer as conductor screen, XLPE insulation, Semi-Conducting layer
           as insulation screen, Semi-Conductive water blocking tape to protect the metallic screen
           area from longitudinal water penetration, Lead sheath with suitable thickness to achieve
           the required cross sectional area that carry the earth fault current and extruded with HDPE
           Sheathed with semi-conducting extruded material.
           •	 Cables are designed and testing according to IEC 60228, 60840 and 60811.

Nominal-    Max. DC                      Non-metallic thickness                          Current Rating         Approx.
 Cross     Conductor                                                           Laid in Ground Laid in free Air   Overall
           Resistance   Operating   Conductor              Insulation  Outer   Trefoil Flat Trefoil Flat        Diameter      Approx
Sectional   at 20 oC   Capacitance   Screen                 Screen     jacket                                                 Weight
  Area
                                               Insulation              mm                                                     Kg/km
                                                                        3.5                                                   11265
mm2 Ω/km μF/km mm mm Mm                                                 3.5    A A AA                           mm            12355
                                                                        3.5                                                   13545
400 R 0.0470 0.241                  1.0        13                1.5    3.5    642 603 844 877                  68            14120
                                                                        4.5                                                   18020
500 R 0.0366 0.264                  1.0        13                1.5    4.5    723 685 1013 997                 71            19100

630 R 0.0283 0.292                  1.0        13                1.5           812 731 1161 1133                74

800 R 0.0221 0.317                  1.0        13                1.5           897 783 1311 1266                79

1000 S 0.0176 0.205                 1.5        13                1.5           1033 860 1544 1467               86

1200 S 0.0151 0.220                 1.5        13                1.5           1106 902 1688 1589               90

           •	 The above data is calculating at 100 % load factor.                                               R: Round
           •	 The above dimensions are subjected to customer request.
                                                                                                                S: Segmental

           •	 The current rating for above table was based on double end bond

           •	 The above data is approximate and subjected to manufacturing tolerance.

           •	 The Aluminum conductor can be submitted according to customer request.