76/132 (145) kV		                                                                          inner semi -con copper wire screen

Single core copper conductor, XLPE                                           cooper conductor outer semi-con                                 HDPE sheathing
insulated, Copper Wires Screen &                                                         XLPE insulation water blocking tape
HDPE sheathed

Description              Stranded circular compacted or segmental conductor with copper or Aluminum material
                         ,Semi-Conducting layer as conductor screen , XLPE insulation , Semi-Conducting layer
                         as insulation screen, Semi-Conductive water blocking tape , to protect the metallic screen
                         from longitudinal water penetration, copper wire as metallic screen to withstand the required
                         earth fault current ,non conductive water blocking tape to protect the metallic screen from
                         longitudinal water penetration, copolymer aluminum tape to protect the cable from radial
                         water penetration and HDPE Sheathed with graphit coating or extruded semi-conducting
                         layer Cables are designed and testing according to IEC 60228, 60840 and 60811.

                                                     Cross         Max. DC Conductor                    Inductance             Approx.
                                                    Seational           Resistance                                              overall
Constructional           Product-Code                                                       Operating   Trefoil  Flat          diameter      Approx.
      Data                                            Area     DC at 20 OC AC at 90 OC     Capacitance                                       Weight
                         G29XC01PH
                         M30XC01PH                   mm2             (Ω/km)  (Ω/km)        (μf/km)      (mh/km)  (mh/km)               mm    kg/km
                         M31XC01PH                  800 R            0.0221  0.0323        0.2247        0.377   0.5156               87.1   13390
                         M32XC01PH                  1000 S           0.0176  0.0234        0.2612       0.3596   0.4982               95.7   16365
                         M33XC01PH                  1200 S           0.0151  0.0205        0.2728       0.3526   0.4913               98.3   17835
                         M34XC01PH                  1600 S           0.0113  0.016         0.2967         0.34   0.4786               103.7  22105
                                                    2000 S           0.009   0.0135        0.3276       0.3263    0.465               110.7  25630
                                                    2500 S                                                                                   31180
                                                                     0.0072  0.0117        0.3606       0.3143   0.4529               118.2

Continous Current Ratings Load Factor = 100% for one circuit in
                             operation (Amperes)

              Laying conditions: trefoil formation                                                  Laying condition: flat formation

                         Direct burial              In air (shaded)                                              Direct burial               In air (shaded)

  Type of      "Cross                                                         Type of       "Cross
 Earthing     Sectional                                                       Earthing     Sectional
  Bonding                                                                     Bonding
  System        Area"                                                         System         Area"

  Cross or       mm2     "pT=120 "pT=150            T = 30 ºC  T = 40 ºC       Cross or     mm2                  "pT=120 "pT=150             T = 30 ºC  T = 40 ºC
single point             T = 25 ºC" T = 35 ºC"                               single point                        T = 25 ºC" T = 35 ºC"
                800 R                                                                      800 R
  bonding      1000 S    872 731                    1329 1200                  bonding     1000 S                938 788                     1521 1376
               1200 S    1045 875                   1639 1479                              1200 S                1115 935                    1859 1682
               1600 S    1124 940                   1777 1604                              1600 S                1203 1009                   2022 1829
               2000 S    1294 1081                  2107 1901                              2000 S                1399 1171                   2424 2192
               2500 S                                                                      2500 S
                         1424 1189                  2359 2128                                                    1555 1301                   2740 2479
                         1565 1306                  2645 2385                                                    1703 1423                   3141 2751

                                                      * R: Round Conductor