Page 130 - 3rd issue
P. 130

intelligent

38 / 66 (72.5) kv                                                                inner semi -con lead sheathed screen

Single Core Copper Conductor                                                 cooper conductor outer semi-con
XLPE insulated,Lead Sheathed                                                             XLPE insulation
Screen and HDPE Sheathed

                                                                                                                                            HDPE sheathing

Description              Stranded circular compacted copper conductor, semi-conducting layer as conductor screen,
                         XLPE insulated, semi-conducting layer as non metalic insulation screen, Semi-conductive
                         water blocking tape to protect the screen area from longitudinal water penetration, lead
                         sheathed with suitable thickness to withstand then reqired earth fault current and HDPE
                         sheathed with graphite coating or extruded semi-conducting layer.
                         Cable are designed and tested to comply with IEC 60228, 60840 and 60811.

                                                     Cross         Max. DC Conductor                        Inductance        Approx.
                                                    Seational           Resistance                                             overall
                         Product-Code                                                       Operating       Trefoil    Flat   diameter      Approx.
                                                      Area     DC at 20 OC AC at 90 OC     Capacitance                                      Weight

Constructional           G25XA01BH                   mm2             (Ω/km)  (Ω/km)        (μf/km)          (mh/km)  (mh/km)  mm            kg/km
      Data               G26XA01BH                  300 R            0.0601  0.0782        0.2241           0.3977   0.5363   57.5          8300
                         G27XA01BH                  400 R            0.047   0.0621        0.2434           0.3814     0.52   60.4          9595
                         G28XA01BH                  500 R            0.0366  0.0496        0.2669           0.3654   0.5041   63.7          11020
                         G29XA01BH                  630 R            0.0283  0.0398        0.2924            0.351   0.4896   67.3          12690
                                                    800 R            0.0221  0.0329        0.3214           0.3372   0.4759   71.4          14935
                         M30XA01BH                  1000 S
                         M31XA01BH                  1200 S           0.0176  0.0236        0.3819           0.3247   0.4633   80.4          18480
                                                                     0.0151  0.0207        0.4002           0.3188   0.4574    83           20100

Continous Current Ratings Load Factor = 100% for one circuit in
                             operation (Amperes)

              Laying conditions: trefoil formation                                           Laying condition: flat formation 	
                                                                                             		
                         Direct burial              In air (shaded)                                                                         In air (shaded)
                                                                                                                     Direct burial
  Type of      "Cross                                                          Type of      "Cross
 Earthing     Sectional                                                       Earthing     Sectional
  Bonding                                                                      Bonding       Area"
  System        Area"                                                          System

Bonded at      mm2       "pT=120 "pT=150            T = 30 ºC  T = 40 ºC       Cross or             mm2              "pT=120 "pT=150        T = 30 ºC  T = 40 ºC
 both end                T = 25 ºC" T = 35 ºC"                               single point                            T = 25 ºC" T = 35 ºC"
              300 R                                                                                 300 R
  Cross or    400 R      532 445                    761 686                    bonding              400 R              562 472              875 791
single point  500 R                                                                                 500 R
              630 R      600 502                    876 789                                         630 R              640 537 1016 918
  bonding     800 R                                                                                 800 R              730 611 1181 1067
              1000 S     674 563 1007 908                                                           1000 S             829 694 1369 1237
              1200 S                                                                                1200 S
                         770 644 1171 1055

                         856 715 1334 1202                                                                             934 780 1580 1427

                         1022 852                   1646 1483                                                        1105 923               1927 1741

                         1095 913                   1778 1602                                                        1190 994               2088 1886

                                                      * R: Round Conductor
                                                    * S: Segmental Conductor

                                                                              Member Pioneer Holding

130
   125   126   127   128   129   130   131   132   133   134   135