Page 72 - Power Cables Catalogue.pdf
P. 72
TECHNICAL INFORMATION
0.6 /1 KV CABLES
CURRENT CARRYING CAPACITY
INSTALLATION IN AIR
A. Factors for variation in ambient temperature:
AIR TEMPERATURE ºC 10 15 20 25 30 35 40 45 50
XLPE 1.15 1.12 1.08 1.4 1.0 0.96 0.91 0.87 0.82
INSULATION PVC 1.22 1.17 1.12 1.07 1.0 0.94 0.87 0.79 0.71
B. Factors for grouping in air.
Single core cables in three phase systems.
In flat formation,clearance = cable In flat formation,clearance = 2d
Arrangement of cables diameter d Distance from wall ≥ 2 cm
Distance from wall ≥ 2 cm
Number of
systems side
by side • • • • • •
Laying on the ground IIV 2 cm d IIV 2 cm 2 d 2 d
d
•••• •••• •••• •••• •••• ••••
Number of
troughs 20 cm 20 cm
Laying on cable • •••• •••• •••• •••• •••• ••••
troughs • •••• •••• •••• d IIV •••• •••• •••• IIV
(restricted air
circulation) • •••• •••• •••• d •••• •••• •••• 2 d 2 d
• •••• •••• •••• IIV 2 cm •••• •••• •••• IIV 2 cm
Number of
grills 20 cm 20 cm
Laying on cable • •••• •••• •••• IIV •••• •••• ••••
grills • •••• •••• •••• d •••• •••• •••• IIV
(unrestricted air
circulation) • •••• •••• •••• d •••• •••• •••• 2 d 2 d
• •••• •••• •••• IIV 2 cm •••• •••• •••• IIV 2 cm
Number of
systems
above IIV 2 cm
each other
• • • d d • • • 2d
Arranged on frameworks
or at walls
•••• •••• •••• •••• •••• ••••
67