Fire Alarm & Extinguishing Systems - 121

Cerberus & Siemens                                                                ASA™ Smoke Detectors Application Guide

Siemens has been involved in fire alarm and extinguishing systems for             High Suppression PS8
over 160 years. Cerberus invented the automatic smoke detector in 1941;           Specifically developed for dance floors in discotheques, live venues and
we have been doing reliable smoke detection longer than anybody else              theatres. Requires a relatively small change in temperature of 8K in
and are a trend setter in detection technology. We employ over 450 people         addition to an alarm signal from the optical chamber to create an alarm.
in R&D and have experience of over 60 million detectors installed around          Provides a much faster response than switching to pure thermal detection.
the world. Our products are reliable and will always be manufactured and          Enhanced safety at critical times where visibility is reduced and large
supported for over 20 years. They will always be backward and forward             numbers of people are in attendance. Complies with the norm EN54-5.
compatible with whatever technology we bring out in the future ensuring           Suppression PS5
the customers’ investment is well protected for the long term.                    Highly robust behaviour, therefore very suitable for applications with
                                                                                  deceptive phenomena such as steam, heavy cigarette smoke or exhaust
Siemens Equipment Range                                                           gases. At the same time the detector reacts with the ASA parameter set
                                                                                  quickly and reliably in case of a real fire due to the dynamic influencing
Digital Addressable Systems                                                       of the parameters. Complies with the norms EN54-5 and EN54-7. For use
                                                                                  in kitchens and production areas with operational related deceptive
This type of system improves collective systems by using loop wiring,             phenomena.
device isolators and software programming to increase reliability and             Suppression CO PS12
provide individual identification of devices in alarm, fault or detector status.  Highly robust behaviour, therefore very suitable for applications with
In addition to the ‘normal’, ‘fire’ or ‘fault’ status, the system is capable of   deceptive phenomena such as steam, heavy cigarette smoke or exhaust
identifying detectors that require maintenance and the status of every unit.      gases. At the same time the detector reacts with the ASA parameter set
This enables optimum service intervals and reduces periodic checks.               quickly and reliably in case of a real fire due to the dynamic influencing
                                                                                  of the parameters. Sensitivity is influenced by the CO concentration.
Siemens Cerberus PRO™ Fire Detection System                                       Separate CO alarming and control for the detection of unhealthy or
                                                                                  dangerous carbon monoxide build up. Complies with the norms EN54-5
Siemens Cerberus PRO™ is a unique fire detection system consisting of             and EN54-7. For use in kitchens and production areas with operational
panels ranging from simple 1 loop to powerful 28 loops to meet all                related deceptive phenomena.
applications from the same system. It can be networked to provide a               High Compensation PS7
seamless system with up to 64 panels - all certified to EN54-13. It provides      Identical to the robust setting except the drift compensation is extended.
normal detectors for standard applications and ASA smoke detectors for            Especially suited for rooms in which a lot of dust and other deposits are
the most demanding of environments. With ASAtechnology™ (Advanced                 expected to build up over a period of time such as paper mills, carpenters
Signal Analysis) reliable smoke detection can now be achieved where               workshops, textile production and recycling plants. Complies with the
previously only heat detectors would be suitable.                                 norms EN54-5 and EN54-7.
                                                                                  Robust PS2
Siemens Cerberus PRO™ Equipment Range                                             Robust behaviour therefore very suitable for applications with deceptive
                                                                                  phenomena such as cigarette smoke, dust and exhaust gases. At the
Includes FC720 Control Panels, neural ASA fire detectors, wide spectrum           same time the detector reacts with the ASA parameter set quickly and
smoke detectors, linear smoke detectors, heat detectors, infrared flame           reliably in case of a real fire due to the dynamic influencing of the
detectors, aspirating smoke detectors and SWING wireless detection.               parameters. Compared to PS5 this set may be used to improve detection
                                                                                  speed on higher ceilings. Complies with the norms EN54-5 and EN54-7.
Voice Evacuation Systems                                                          For use in event locations, conference rooms, smoking rooms,
                                                                                  gastronomy, industry production and underground garages.
The Siemens E100 VA System is a digital voice actuated alarm and                  Balanced PS4
evacuation system, available as a stand-alone model or fully networked            For use in normal environments. Balanced response characteristic,
and integrated to the fire alarm system. European standards recognise             sensitive in the case of fire, robust with deceptive phenomena. Due to its
that voice evacuation is an integral part of fire detection and needs to be       distinct dynamic the detector reacts quickly to open fires and smouldering
treated with the same high standards.                                             fires according to the definitions of EN54. The ASA parameter set reacts
E100 complies fully with EN60849: electro-acoustical emergency warning            very robustly to deceptive phenomena such as cigarette smoke or small
systems and EN54-16 components for voice-actuated alarms in fire alarm            amounts of steam. Often used when system is unmanned mode e.g. at
systems and voice-actuated alarm centres.                                         night. Complies with the norms EN54-5 and EN54-7. For use in open plan
                                                                                  offices, hallways, hotel rooms, out of hours use in harsh environments.
Graphical Management Package                                                      Balanced CO PS10
                                                                                  Using the criteria smoke, heat and CO the device is more sensitive to
Siemens MM8000 is a professional danger management and monitoring                 fires creating CO than PS4 without the CO signal. This parameter set is
system for integrating security and safety systems, providing event history       robust with deceptive phenomena such as cigarette smoke or small
and analytical reports. It can be configured to provide text only display of      amounts of steam. It also offers early alarming in the event of fires
the entire subsystems or full graphical representation of protected areas.        generating a large amount of CO such as mattress fires. Complies with
                                                                                  the norms EN54-5 and EN54-7. Same applications as with PS4 but with
Current Fire Detection Standards                                                  higher robustness against deceptive phenomena.
                                                                                  Fast Response PS6
All components of the Cerberus PRO System fully comply and are certified          This parameter set reacts in a fast and highly sensitive manner. It is
by VdS or LPCB for CPR (Construction Product Regulation) introduced               especially suited for rooms without deceptive phenomena where the
from 1st July 2013.                                                               priority is on detecting fire as early as possible and is an excellent
BSEN54-13 - Complete system compatibility test.                                   replacement for ionisation detectors. For use in high ceilinged rooms,
BS-5839 - Part 1:2013 : Fire detection and alarm systems in buildings.            storage rooms, warehouses with highly flammable material, IT rooms,
EN-54 - Parts 2 & 4:1998 : Power supplies and control/indicating equipment        control of extinguishing systems. Complies with the norms EN54-5 and
including all Options With Requirements (OWRs).                                   EN54-7.
BSEN-54 - Various parts covering detection and alarm devices.                     High Sensitive Fast PS9
BS-7273 - Part 4 including Category A.                                            This parameter set allows for the fastest possible detection for both open
                                                                                  and smouldering fires. It is intended for use in clean applications with no
Sinorix™ Intelligent Extinguishing Solutions                                      deceptive phenomena such as hospital rooms, museums, operating
                                                                                  rooms, rooms with high ceilings where high sensitive detection is of great
The comprehensive Sinorix extinguishing portfolio for room and object             importance. Complies with the norms EN54-5 and EN54-7.
protection comprises solutions with natural or chemical extinguishing
agents, gas/water-combined as well as water mist solutions. Our range
includes:
Sinorix N2 Ar CO2 - Automated extinguishing solutions with natural agents.
Sinorix CDT - Automated extinguishing solution with nitrogen providing
constant gas discharge.
Sinorix al-deco PLUS - Safe object protection system for machine tools.
Sinorix al-deco STD - Object protection system for machine tools.
Sinorix 1230 - Automated extinguishing solution based on chemical agent
Novec 1230.
Sinorix 227 - Automated extinguishing solution based on extinguishing
agent HFC-227ea.

Siemens Building Technologies        Tel : 01276 690207

Fire Safety Products - Cerberus PRO

Brunel House

Sir William Siemens Square

Frimley Surrey                 Website : siemens.co.uk/cerberus

GU16 8QD        Email : cpssalessupport.sbt.uk@siemens.com