118 - Leak Detection - System Design Guide

Floodline                                                                      Floodline 4 Zone Control Panel

The Andel “FLOODLINE” range covers all possible requirements, from             Leader Cable LSF-0H                  Zone 3                                      Zone 1
stand-alone single zone modules and units for the smaller installation, to     Multi-8 Zone Detection Cable                                 Zone 2
comprehensive multi-zone systems with the capacity to handle the largest
building offering outstanding flexibility, with a range of equipment and       “Plug and Play” Start of Line (SOL)
sensors to tailor each installation to the client's exact needs.               “Plug and Play” Autocoupler (Auto)
                                                                               “Plug and Play” End of Line (EOL)
SENSOR SELECTION:                                                              Point Sensor
Choosing the best sensor to suit the application and the areas to be
monitored:                                                                     Oil Sensor

Multi - 8 Zone Detection Cable:                                                CONTROL PANEL SELECTION:
Within raised floor voids in data centres, comms / server / IT rooms,          Small:
teapoints and vending areas, drip trays, A/C units and underfloor pipework.    Up to 20m of Detection Cable in the raised floor void of one room, within
                                                                               a short length of drip tray, 1 - 3no Point / Oil Sensors, usually within the
Multi - 4 Zone Detection Cable:                                                same room or 1no FGS1000 Ref. Gas Sensor.
Attach along the full length of high level pipework especially above critical  - Floodline One Zone Control Panel - Volt free outputs for ‘LEAK’ and
/ sensitive areas.
                                                                                 ‘SYSTEM’ fault.
Point Sensor:
Plant rooms, tank rooms, trenches, small drip trays, base of lift shafts,      Medium:
toilets and showers.                                                           20 - 300m of Detection Cable either within single or multiple rooms, several
                                                                               A/C Units or separate Drip Trays and combination of between 5 - 50no
Flexi-Pad:                                                                     Point / Oil Sensors in large Plant / Generator Rooms and 4 - 20no
Pipe joints and junctions, plumbed in water coolers and inaccessible areas.    FGS1000 Ref. Gas Sensors, etc.
                                                                               - Floodline 4 - 32 Zone Control Panels – Volt free outputs for ‘LEAK’ and
Pipe-in-Pipe Sensor:
Double containment water pipework and tanks and high level alarm.                ‘SYSTEM’ fault and individual zone output relays available.

DP01 Double Containment Sensor:                                                Large:
Double containment oil / diesel pipework and tanks, either along full length   Over 300m of Detection Cable either within a large area (data centre) or
or at lowest point.                                                            across many smaller room (server and comms rooms) and/or combination
                                                                               of Point / Oil / Ref. Gas Sensors.
Oil Sensor:                                                                    - Floodline 128 System - 32 / 64 / 96 / 128no Zones – Volt free outputs
Bunded oil storage tanks, generator rooms and oil pipework trenches.
                                                                                 for ‘LEAK’ and ‘SYSTEM’ fault, RS232 / 485 + MODBUS and individual
FGS1000 Refrigerant Gas Sensor:                                                  zone output relays available.
Office areas served by VRF / VRV units, in chiller plant rooms, along
refrigerant gas pipework routes.                                               Floodline 16 Zone Control Panel

SYSTEM LAYOUT:                                                                 A/C UnitZone 2                                    Zone 7                                                        Zone 11
Choosing the best design for optimum coverage with the most suitable sensor:   Comms Room                           Zone 6                                                                Zone 12
                                                                                     Zone 1
Perimeter:                                                                                                         ZoneZone 4Plant
Install Multi - 8 Zone Detection Cable in the raised floor void attached to                                                         Zone 8
the floor slab approx. 500mm in from the wall.                                                                                     A/C UnitZone 5
                                                                                 Kitchen                            Zone 10 Zone 9
Whole Floor Area:                                                                                                                                                            Oil Tank bund
Install Multi - 8 Zone Detection Cable in the raised floor void across the
whole floor space at 2m centres.                                               ACCESSORIES:
                                                                               Various options for connecting components, installing the Floodline sensors
A/C Units / Downflow Units:                                                    and control panels and adapting the system for each individual site:
Install Multi - 8 Zone Detection Cable either around the ‘footprint’ of the
unit or ‘zig-zagged’ directly beneath.                                         Zone Couplers:
                                                                               Start / Auto / End of Line – Using RJ48 connectors for ease of installation
Low Level Pipework in Floor Void:                                              by simple ‘plug & play’ connectivity.
Install Multi - 8 Zone Detection Cable beneath the pipework within the
floor void in a ‘serpentine’ pattern along the full pipe length.               Junction Boxes:
                                                                               For use with Multi - 4 Zone Cable to connect from panel to the first zone
High Level Pipework:                                                           and then between each concurrent or separate zone.
Attach Absorbent Multi - 4 Zone Detection Cable to the underside of the
whole pipe length outside any lagging.                                         Leader Cable:
                                                                               Full LSF - 0H interconnecting cable for use from the control panel to each
Plant Room:                                                                    individual or set of zones.
Install Point Sensors either at equidistant positions around the room or
targeted at specific items of equipment e.g. Pump Sets, Water Tanks, etc.      Remote Panel:
                                                                               Provides audible and visual alarm at a secondary position i.e. at a
Double Containment Pipework:                                                   reception desk or security office.
Install DP01 Pipe-in-Pipe Sensor at equidistant positions along the full
pipe lengths - usually 10-15m apart or at the lowest point if the pipework     Caution Tags:
runs to a fall.                                                                Usually fitted every 1-2m along clearly identifying detection cable.

Refrigerant Gas:                                                               Clips:
Within offices, install at mid level (approx. 1m from floor) preferably        Self-adhesive 6.3mm clips or drilled and plugged ‘P’ clips usually installed
adjacent / near to VRF units. For Chiller Rooms, etc. install every 6m3        every metre and every change of direction along the full length of the
across the whole area.                                                         detection cable.