116 - AEI Cables Technical Data for Total Fire Solutions
Firetec Singlecore
No. of cores & Nominal Current Rating (Enclosed in Conduit) Voltage Drop Maximum DC Conductor Nominal Overall Nominal Weight
CSA of Conductor Resistance@ 20°C Diameter
Single Phase ac or dc Three Phase ac dc Single Phase ac Three Phase ac Kg/Km
no x mm² Ω/Km mm 26.00
1 x 1.50 Amps Amps mV/AM mV/A/M mV/A/M 12.10 3.50 38.00
1 x 2.50 22.00 19.00 31.00 31.00 27.00 7.41 4.10 54.00
1 x 4.00 30.00 26.00 19.00 19.00 16.00 4.61 4.6 75.00
1 x 6.00 40.00 35.00 12.00 12.00 10.00 3.08 5.10 124.00
1 x 10.00 51.00 45.00 7.90 7.90 6.80 1.83 6.70 183.00
1 x 16.00 71.00 63.00 4.70 4.70 4.00 1.15 7.60 285.00
1 x 25.00 95.00 85.00 2.90 2.90 2.50 0.73 9.40
126.00 111.00 1.90 1.90 1.65
Firetec Standard
No. of cores & Current Rating (Clipped Direct) Voltage Drop Maximum DC Nominal Nominal Recommended Accessories
Nominal XSA of Single Phase ac or dc Three Phase ac Conductor Overall Weight
dc Single Three Phase ac Diameter Clips Glands Shrouds
Conductor Phase ac Resistance@ 20°C Kg/Km
mV/AM mm 87.00 FCL30 FG1 FXG20
no x mm² Amps Amps 29.00 mV/A/M mV/A/M Ω/Km 7.70 129.00 FCL34 FG1 FXG20
2 x 1.50 19.50 - 18.00 12.10 9.10 110.00 FCL32 FG1 FXG20
2 x 2.50 27.00 - 29.00 - 7.41 8.20 163.00 FCL37 FG2 FXG20
3 x 1.50 - 12.10 9.70 139.00 FCL34 FG1 FXG20
3 x 2.50 - 17.50 - 18.00 - 7.41 9.20 210.00 FCL43 FG2 FXG20
4 x 1.50 - 24.00 - 12.10 10.90
4 x 2.50 - 17.50 - - 25.00 7.41
- 24.00
- 15.00
- 25.00
- 15.00
Firetec Enhanced
No. of cores & Current Rating (Clipped Direct) Voltage Drop Maximum DC Nominal Nominal Recommended Accessories
Conductor Overall Weight
Nominal XSA of Single Phase ac or dc Three Phase ac dc Single Three Phase ac Diameter
Phase ac Resistance@ 20°C Kg/Km
Conductor mV/AM mm 103.00 Clips Glands Shrouds
29.00 Ω/Km 9.10 140.00
no x mm² Amps Amps 18.00 mV/A/M mV/A/M 12.10 9.70 135.00 FCL34 FG1 FXG20
2 x 1.50 19.50 - 29.00 - 7.41 9.60 186.00 FCL37 FG1 FXG20
2 x 2.50 27.00 - - 18.00 - 12.10 10.70 165.00 FCL37 FG1 FXG20
3 x 1.50 - 7.41 10.70 234.00 FCL43 FG2 FXG20
3 x 2.50 - 17.50 - - 25.00 12.10 11.90 FCL40 FG2 FXG20
4 x 1.50 - 24.00 - - 15.00 7.41 FCL47 FG2 FXG20
4 x 2.50 - 17.50 - 25.00
- 24.00 - 15.00
Firetec Power
No. of cores & Current Rating Voltage Drop Maximum DC Gross CSA of Armour Nominal Overall Nominal Weight
Nominal XSA of Single Way Ducts Three Phase ac Conductor Diameter
Laid Direct Free Air Kg/Km
Conductor Resistance@ 20°C mm 367.00
13.30 454.00
no x mm² Amps Amps Amps mV/A/M /Km mm² 14.70 556.00
16.00 783.00
4 x 1.50 32.00 26.00 26.00 27.00 12.10 17.00 18.20
4 x 2.50 42.00 34.00 35.00 16.00 7.41 20.00
4 x 4.00 55.00 45.00 47.00 10.00 4.61 22.00
4 x 6.00 69.00 56.00 107.00 6.80 3.08 36.00
Current Ratings for 4x 10.0 to 4x 400.0 sqmm please refer to Firetec Impact Power. For further constructional information refer to our website www.aeicables.co.uk
Firetec Impact Power Laid Direct Current Rating Free Air Voltage Drop Maximum DC Gross CSA of Armour Nominal Overall Nominal Weight
Conductor Diameter
No. of cores & Amps Single Way Ducts Amps Three Phase ac mm² Kg/Km
Nominal XSA of Resistance@ 20°C mm
55.00 Amps 47.00 mV/A/M 42.00 812.00
Conductor 69.00 59.00 Ω/Km 42.00 20.00 853.00
92.00 45.00 82.00 10.00 42.00 20.00 1029.00
no x mm² 119.00 56.00 107.00 6.80 4.61 50.00 20.00 1367.00
152.00 75.00 140.00 4.00 3.08 70.00 22.50 2240.00
4 x 4.00 182.00 96.00 172.00 2.50 1.83 78.00 29.90 2705.00
4 x 6.00 217.00 124.00 209.00 1.65 1.15 90.00 33.50 3375.00
4 x 10.00 266.00 149.00 363.00 1.15 0.73 131.00 37.10 4560.00
4 x 16.00 319.00 177.00 324.00 0.87 0.52 147.00 39.10 5805.00
4 x 25.00 363.00 218.00 376.00 0.60 0.39 206.00 43.00 7430.00
4 x 35.00 406.00 263.00 430.00 0.45 0.27 230.00 48.30 8820.00
4 x 50.00 458.00 300.00 495.00 0.37 0.19 255.00 52.40 10600.00
4 x 70.00 529.00 338.00 584.00 0.30 0.15 289.00 56.60 13380.00
4 x 95.00 592.00 382.00 666.00 0.26 0.12 319.00 64.30 16255.00
4 x 120.00 667.00 442.00 766.00 0.21 0.10 452.00 70.70 21145.00
4 x 150.00 496.00 0.19 0.08 80.30
4 x 185.00 570.00 0.17 0.06
4 x 240.00 0.05
4 x 300.00
4 x 400.00
Firetec FRF2 Current Rating (Enclosed in Conduit) Voltage Drop Maximum DC Nominal Overall Nominal Weight
Conductor Diameter
No. of cores & Nominal Single Phase ac or dc Three Phase ac dc Single Phase ac Three Phase ac Kg/Km
XSA of Conductor Resistance@ 20°C mm 135
Amps Amps mV/A/M mV/A/M mV/A/M 10.00 168
no x mm² 34.10 34.10 - Ω/Km 11.20 149
3 x 1.50 23.00 - 20.90 21.00 - 13.30 11.20 211
3 x 2.50 31.00 - - - 7.98 12.40
4 x 1.50 21.00 - - 29.70 13.30
4 x 2.50 - 28.50 17.60 7.98
-
Mineral Insulated
Conductors Cables exposed to touch Sheath Earth Fault Maximum Cable diameter Cable weight Recommended accessories
effective loop conductor (mm) (Kg/km)
Cable ref Size Current rating (amps) Volt drop resistance Glands & seals Copper fixings
(mm2) MV/A/m CSA impedance (ohm/km at Bare LSZH Bare LSZH
No (mm2) (R1+R2)
(ohms/m) 20°C)
Bare LSF covered Gland ref RGM One hole clips Two-way saddles
2L1.5 2 1.5 21.0 23.0 28.0 6.3 21.2 12.1 5.7 7.0 131 154 20 20 22 28 222 302
2L2.5 2 2.5 28.0 31.0 17.0 8.2 13.3 7.4 6.6 7.9 180 206 20 20 26 32 272 342
3L1.5 3 1.5 17.0 19.0 24.0 7.8 20.6 12.1 6.4 7.7 168 194 20 20 24 30 272 342
3L2.5 3 2.5 23.5 26.0 14.0 9.5 12.9 7.4 7.3 8.8 222 272 20 20 28 34 302 342
4L1.5 4 1.5 17.0 19.0 24.0 9.1 20.2 12.1 7.0 8.3 203 231 20 20 28 34 302 342
4L2.5 4 2.5 23.5 26.0 14.0 11.3 12.5 7.4 8.1 9.6 286 336 20 20 32 37 342 422
2H1.5 2 1.5 22.5 25.0 28.0 11.0 19.8 12.1 7.9 9.4 224 259 20 20 30 37 342 382
2H2.5 2 2.5 31.0 34.0 17.0 13.0 12.4 7.4 8.7 10.2 275 314 20 20 34 40 342 422