Page 46 - Arebian
P. 46
46
Delta P across Evaporator,Kg/cm2 1.4 Kg/cm2(g) 1.4 Kg/cm2(g)
Air cooled Condenser Air cooled Condenser Air cooled Condenser
Observed condenser Less than 5 Less than 5
approach,deg.cen
Observed Avg. Compressor power,kW 112.8 Kw 85.8 Kw
Observed Flow,Cu.mtr/hr 203.57 Cu.mtr/hr 144.45 Cu.mtr/hr
Velocity/s 4.58 m/s 3.23 m/s
Existing Heat load ,TR 80.78 TR (2,44,284 66.87 TR (2,02,230
kCal) kCal)
Specific Energy consumption,kW/TR 1.396 kW/TR 1.283 kW/TR
1.256
4 Chilled water Circulation Pump
Details
No. of chilled water circulation pumps 5,
Pump status Pump no.2, 3, 4&5 are in running condition
and pump no.1 is in off condition.
Make York
Type Horizontal Centrifugal coupled type
Model NA
Sr.no Description Observations
Sr.no. NA
Capacity M3/hr NA
Head Mtr NA
Size 80 mm X 65 mm
RPM 1450 rpm
Motor HP/Kw 20 HP / 15 Kw