Page 171 - policy and procedure infection control
P. 171
Policies and Procedures on Infection Control
• Select the differential count size on the menu
• Place the counter on the OT table and press start
• Take the reading once the reading stops.
• The reading should be very minimum under the air curtain.
• Measure at the center and at each of the 4 quadrants.
• Results 0 for particles > 0.5um.
5. Report on completion of the commissioning
• Contents
• Description of the OT room, reasons for testing, general nature of tests
performed
• Summary of test results and observations
• Conclutions and recommendations
• Tabulated results with interpretations
Example of report
HRPZ II MICROBIOLOGY REPORT
Subject: Recommissioning of OT Intan, and Zamrud following repair work done on ceilings due to
leaking.
There are 4 OT rooms in OT intan (Intan 1, 2,3 & 4) and 2 OT rooms in OT Zamrud ( Zamrud 1 & 2)
Site : 1st floor New OT Complex Date : 21.07.08
Theater : Intan 1
Temperature : 20 0 C Humidity : 52 %
Air changes : 20 ACH
160 Ministry of Health Malaysia