Page 171 - policy and procedure infection control
P. 171

Policies and Procedures on Infection Control


                            •  Select the differential count size on the menu
                            •  Place the counter on the OT table and press start
                            •  Take the reading once the reading stops.
                            •  The reading should be very minimum under the air curtain.
                            •  Measure at the center and at each of the 4 quadrants.

                            •  Results 0 for particles > 0.5um.
                         5. Report on completion of the commissioning
                            •  Contents
                            •  Description of the OT room, reasons for testing, general nature of tests
                              performed
                            •  Summary of test results and observations
                            •  Conclutions and recommendations
                            •  Tabulated results with interpretations




               Example of report



               HRPZ II MICROBIOLOGY REPORT
               Subject: Recommissioning of OT Intan, and Zamrud following repair work done on ceilings due to
               leaking.
               There are 4 OT rooms in OT intan  (Intan 1, 2,3 & 4) and 2 OT rooms in OT Zamrud ( Zamrud 1 & 2)
               Site        : 1st floor New OT Complex                   Date       :  21.07.08
               Theater     : Intan 1

               Temperature : 20 0 C                                     Humidity   :  52 %
               Air changes : 20 ACH




















                 160  Ministry of Health Malaysia
   166   167   168   169   170   171   172   173   174   175   176