Page 172 - policy and procedure infection control
P. 172

Policies and Procedures on Infection Control



                        Test performed                        Result                   Comment
                  1. Inspection of control and  In good condition                      Complies
                     warning devices within
                     the OT

                  2. Bacterial count          21 cfu / m3                              Complies

                  3. Leakage around or        No evidence of leak                      Complies
                     through HEPA filter
                     (detection by means of
                     Electronic   Particle
                     Counter)

                  4. Smoke tests              1. There is a good airflow in all 4 quadrants  Complies
                                              2. There are no areas of gross turbulence
                                                 observed
                                              3. There is a clear movement of air from the
                                                 OT table towards the periphery and out
                                                 through the outlet fins and from inside
                                                 the OT room to the outside room.





                Interpretation of results :  ………………………...……...…………………………………………


                Conclusions           :  …………………………..……………………………………………….

                Recommendations       :  ……………………………..…………………………………………….



























                                                                          Ministry of Health Malaysia  161