                  7.2  Task 2: Lighting – Closed Loop Control Master-Slave with
                        separate Actuator

                  Illumination level at a workplace shall be kept constant at 500 lux. Additionally it should be
                  possible to change the parametrised luxvalue setpoint (300 – 800 lux), and the light shall
                  be also manually operable (i.e., automatic / manual changeover shall be possible).
                  As a device for this task the brightnesscontroller type Siemens UP255 shall be used.
                  During the commissioning procedure it has to be calibrated, to adopt it to the prevailing
                  light- and reflexion conditions.
                  Process description see further below!

                  A device to control shall be a 4-gang push button which also can set 16 bit values, or a
                  suitable binary input or a push button interface.

                  Functions of this 4-gang push button:

                  Rocker A: lighting manually on/off + dimming
                  Rocker B: Automatic on/off
                  Rocker C: Presence on/off
                  Rocker D: Upper button setpoint 600 lx; lower button setpoint 400 lx

                  Alternatively (and much better) a display and operation unit would be recommendable,
                  where beside the normal operating functions you can also see the current brightness level
                  indication, and which permits a nearly continuous adjustment of the setpoint.

                  Example: Siemens 5WG1585-2AB11 (UP 585) Display- and operation unit.

                  Project design

                      Create the following group addresses

                      •  Licht E on/off
                      •  Light F on/off
                      •  Light E dimming
                      •  Light F dimming
                      •  Sensor setpoint adjust
                      •  Calibration trigger
                      •  Automatic control on/off
                      •  Presence on/off
                      •  Dimmvalue set auto Licht E
                      •  Dimmvalue set auto Licht f

                      Parametrise and link the bus devices
                      Check the necessary read flags in the sensor UP255 and the S/D actuator
                      Use default settings of the device if not otherwise defined