Page 193 - Advanced Course
P. 193

KNX ADVANCED COURSE

                  Used devices

                      Brightness controller UP255                   25 S1 Brightness control 909601
                      Push button 4-gang delta profile      12 S4 On/Off/Dim/Blnd/Displ241301
                      Dimming actuator like in the basic project

                  Commissioning

                      Save your work
                      Download the devices and test


                  7.3  General hints for the calibration of lighting closed loop control


                      1)  Start ETS
                      2)  Open the required dim actuators, configure their parameters, create the groups
                         and link them, finally download to the actuator
                      3)  Configure the brightness controller as well: depending on your preference with a
                         fixed setpoint (parameter) or a variable one by object.
                      4)  Don’t forget to link the object “calibration” to a group address!
                      5)  Now adjustment at 50% operating point follows: Prerequisite: External light level in
                         the room >= 50% of setpoint.
                      6)  To achieve that, switch on the lights and close the shutters
                      7)  Now place a precision luxmeter underneath the sensor
                      8)  Then adjust the measured luxvalue at the sensor that it shows approx. 50% of the
                         setpoint. Example: >= 250 lx at setpoint of 500 lx. Best results are made when
                         direct value control (8 bit) is used to set the required dimming value instead of 4-bit
                         dimming.
                      9)  It must be ensured that daylight level is constant enough
                      10) When the luxmeter now shows the correct setpoint, simply send a telegram to let it
                         calibrate. (this can be achieved either by ETS, or a test push button)
                      11) The controller should respond with the parameterised setpoint. Now the control is
                         calibrated and can be used.
                      12) If there is no controller feedback, then the reason can be: value out of range,
                         caused by too bright or too dark surface, too much side light
























                  Home and Building Management Systems                                    KNX Association
                  Lighting Control                  Lighting Control_E0310a.doc                      34/34
   188   189   190   191   192   193   194   195   196   197   198