Chapter 5 Cold water systems


                 g  HUK1  Hose union bib tap incorporating a double check   3     3
                          valve arrangement; permitted only as a replacement
                          for existing bib taps in house installations
                 h  HC    Diverter with automatic return (normally integral   X   3
                          with some domestic appliance applications only)

                Notes:
                ‘X’ indicates that the backflow prevention device is not acceptable for protection against back pressure
                for any fluid category.
                Arrangements incorporating a type DB device shall have no control valves on the outlet of the device.
                The device shall not be fitted less than 300 mm above the spill-over level of an appliance and must
                discharge vertically downwards.
                Relief ports from BA and CA devices should terminate with an air gap, the dimension of which should
                satisfy a type AA air gap.

                Type BA verifiable backflow preventer with reduced
                pressure zone (a reduced pressure zone valve)
                Better known as an RPZ valve, this is a mechanical, verifiable, backflow prevention
                device, offering protection to water supplies up to and including fluid category 4.
                Verifiable simply means that the valve can be checked via test points to see if it is
                working correctly (verified).



                   Valve open                          Valve open
                 Normal
                direction
                of flow
                                                              Normal direction of flow











                                 Relief port  Valve closed
                                      Valve closed                        Valve open



                    Normal direction of flow
                                                                           Direction
                                                                           of
                                                                           backflow







                Type BA or reduced pressure zone valve
                (RPZ valve).                               Valve open
                Suitable for protection against fluid category:  Relief port

                     Back             Back
                  4               4
                     pressure         siphonage
                p  Figure 5.76 An RPZ valve cut-away
                                                                                                                303