Page 44 - РЕЛЕ ҲИМОЯСИ БЎЙИЧА УМУМИЙ ТУШУНЧАЛАР
P. 44
Minimal kuchlanish relesi PH-54-160 tanlaymiz.
Liniyaga o’rnatilayotgan maksimal tokli himoyani hisoblaymiz.
2.7.5 Maksimal tokli himoya
Himoyaning ishlash toki:
k k 1,2 2
I II z uz .ish I 66 198A.
him .ish ish .max
k 0,8
qay
Relening ishlash toki:
I II 198
I II k him .ish 1 3,3A.
.ish
rele
sx
n 60
tt
Himoyaning sezgirligi:
10
I (2) 1937
t
k q . .min.tash 35 2,87 1,5.
sez
II
I rele .ish n tt 3,3 60
Himoyaning ishlash vaqti:
t II t I t 0,6 0,5 1,1s.
him .ish him .ish
2.7.6 O‘ta yuklanishdan himoya
O‘ta yuklanishdan himoya habar berishga ishlaydi.
Himoyaning ishlash toki:
k 1,05
I z I 66 86,63A.
.ish
him
k qay n .t 0,8
Himoya RT – 40 va RV – 200 relelar yordamida bajarilib, u bitta fazaga
ulanadi.
O‘ta yuklanishdan himoyaning vaqti maksimal tokli himoyaning vaqti bilan
muvofiqlantirilishi loziv:
II
I
t him .ish t him .ish t 1,1 0,5 1,6s .
46