Sr.no. Description Thermic fluid heater no.1/2/3
Status Thermic fluid heater no.3 is on and other 2
& 3 are in shut off condition.
29 Power taken by thermic fluid heater, 42.53 Kw
Kw
30 Power factor 0.88
31 Voltage 402.8 volts
32 Fuel consumption measurements
33 Initial tank level, mm 360 mm
34 Initial tank volume, lit 6555.816 lit
35 Final tank level, mm 345 mm
36 Final tank volume, lit 6282.657 lit
37 Fuel consumption during trial from 273.159 lit
01:36 to 05:36 hrs-total duration of
burner on time- 1.5 hrs
38 Specific gravity of fuel (Diesel) 0.846
39 Fuel consumption kg/hr 154.06 kg/hr
40 Heat given by fuel kcals/hr 1596989 kcals/hr
41 Heat taken by thermic fluid kcals/hr 1250122 kcals/hr
42 Thermal Efficiency 78.27%