Page 54 - Arebian
P. 54

54







                Sr.no.    Description                            Thermic fluid heater no.1/2/3

                          Status                                 Thermic fluid heater no.3 is on and other 2
                                                                 & 3 are in shut off condition.

                29        Power taken by thermic fluid heater,  42.53 Kw
                          Kw

                30        Power factor                           0.88

                31        Voltage                                402.8 volts

                32        Fuel consumption measurements

                33        Initial tank level, mm                 360 mm

                34        Initial tank volume, lit               6555.816 lit

                35        Final tank level, mm                   345 mm

                36        Final tank volume, lit                 6282.657 lit
                37        Fuel  consumption  during  trial  from  273.159 lit
                          01:36  to  05:36  hrs-total  duration  of
                          burner on time- 1.5 hrs

                38        Specific gravity of fuel (Diesel)      0.846

                39        Fuel consumption kg/hr                 154.06 kg/hr

                40        Heat given by fuel kcals/hr            1596989 kcals/hr

                41        Heat taken by thermic fluid kcals/hr   1250122 kcals/hr
                42        Thermal Efficiency                     78.27%
   49   50   51   52   53   54   55   56   57   58   59