SECTION 5.0 – ARCHITECTURAL COMPONENTS, MATERIALS AND FINISHES   SECTION 5.0 – ARCHITECTURAL COMPONENTS, MATERIALS AND FINISHES



 5.13.4   Generally, paints and stains with low VOC content will be used and shall
 be of the required quality and standard obtained from local manufacturers   5.13.15  All walls in the clinical work areas and sterile areas such as laboratories,
 and of the PD’s concurrence.     treatment rooms, CSSD, OT area, clean utility rooms, etc., shall be painted
                                  with approved epoxy paint or polyurethane paints with low VOC content
 5.13.5   Before painting works, the wall panel surface shall be completely dry, free   and shall be to the PD’s concurrence.
 from dust, dirt, etc. Painting to other surfaces and works shall conform to
 the latest JKR’s  General Specifications for Building Works’  minimum   5.13.16  CSSD and other sterile areas that specify painting works shall be painted
 standards.                       with approved low VOC content and shall be to the PD’s concurrence.

 5.13.6   Silicone-based water repellents paint where specified shall conform to BS   5.13.17  The minimum requirement for all areas shall be as follow:
 3826 Class A.
                                  a) All clinical including wards and sterile departments shall be painted with
 5.13.7   All metal surfaces shall be powder coated unless otherwise stated.  All   epoxy paints.
 metal surfaces other than powder coated or anodised shall be, coated with
 one undercoat anti-rust and  finished with two  coats of approved gloss   b) All administrative, corridor, and public areas at non-clinical areas shall
 enamel paint and to the manufacturer’s specification.   be painted with washable paint.

 5.13.8   Finishes for timber shall be lime-washed, stained, or painted with approved   c)  All stores unless otherwise specified and M&E services rooms shall be
 gloss paint wherever appropriate.   painted with emulsion paint.

 5.13.9   Exposed timber shall be primed with primers conforming to MS 132: UDC
 667.649 Specification for Undercoating Paint for Use Under Gloss Enamel   CHECKLIST OF WALL PAINT
 Paint, applied with 2 coats of approved stain, and coated with flat varnish.
                                                                                TYPE OF PAINT
 5.13.10  All external walls shall be painted with weather-resistant and anti-fungus
 properties. The contractor may also propose other types of external wall   NO.   AREAS/ROOMS   Weather   PU/
 finishes, fungus-free and require minimum maintenance. The external walls   resistant   Epoxy   Washable
                                                                         & anti-
 painting proposal shall  be enclosed with a performance warranty  for a   fungus     paint      paint
 minimum of ten (10) years.

 5.13.11  All internal walls, excluding clinical departments, shall be painted with   1   External wall   √
 washable paint type. Heavy circulation areas, including corridors, shall be
 painted with paints that are easily washable and maintainable.
                                    2    Internal wall:
 5.13.12  All walls for 24 hours air-conditioned rooms shall be painted with PU or   24 hours areas/room   √
 epoxy paint as stipulated in the latest JKR’s Guidelines on The Prevention   Example of related
 of Mould Growth in Buildings.           departments/ rooms:
                                         a)  A&E Department
                                         b)  OT Department
 5.13.13  Storage areas wall shall be painted with washable emulsion paint to the   c)  In-Patient Department
 manufacturer’s specifications and the PD’s concurrence.   d)  Pharmacy store
                                         e)  Others as stated in MBOR
 5.13.14  All non-clinical walls to public and semi-public areas such as corridors, sub   or technically required
 waiting areas, and waiting lounge shall be finished with approved washable
 emulsion paints with low VOC content and shall be  to  the PD’s
 concurrence.