                             5  Summary of Energy Saving Opportunities In The Plant




               The plant is found to be taking continuous actions to optimize the energy consumption as well
               as adopting new technologies.

                   This energy Audit  is one  of the  parts  of the energy conservation  initiatives taken by the
               plant  wherein  efforts  are  taken  to  measure  the  efficiencies  of  energy-intensive  equipment,
               establishing specific energy consumption benchmarks and remedial actions for optimization of
               energy costs (Both Fuel and Electricity).


               Observations and recommendations are given below.

                1.  Arabian  Flexible  Packaging  uses  electricity  +  Diesel  as  the  main  energy  source  for  the
                    production.
                2.  Electrical  energy  consumption  per  month  of  the  plant  is  approximately  488663.5kWh
                    which cost approximately 185692 AED Per Month at 0.38 AED /KWH. (Ref. Table No. 2)

                3.  The Supply Electricity Board have implemented Cost Reflective Tariff Structure which has
                    resulted in a rise in electricity bill.
                4.  Total  average  Diesel  (fuel)  consumption  is  11000  liter  per  month  for  Boilers.  This  is
                    considerable Energy use (Equivalent to 115,500,000 Kcal or 134302 KWH).
                5.  Fuel consumption data needs to be further clear i.e. clear figures in terms of Consumption
                    in gallons / liters per month.
                6.  The linear relation between Energy Consumption and production in the period of Jan-18 to
                    Dec-18  y=  28.16x  +  458254  (Refer  Figure-2).  which  means  the  variable  component  of
                    energy  (Varying  with  respect  to  production  is  very  small  as  compared  to  the  fixed  one.
                    Fixed component is almost 85% of the total energy consumption.
                7.  The scatter on the graph shows that there is not control on Energy Vs. Production.

                8.  Feb-2018 was the best energy performance month of the plant where Energy Performance
                    was i.e. 340 KWH / MT and August 2018 was the worst energy performance month with
                    figure of 535 KWH / MT. Of course this has weather impact, however, considering the low
                    or  almost  similar  ambient  temperatures  in  Month  of  January,  February,  March,
                    considerable deviation is seen in the SEC.
                9.  The  plant  would  have  saved  almost  1.32  Million  KWH  Units  (App.  0.5  Million  AED)
                    statistically if the plant energy performance would have been at par to the best one (340
                    KWH/MT). Though this data is statistical, but is a fact and should be considered as bench

                    mark for the factory. This also indicates the need of keen monitoring of SEC Per Month, Per
                    Hour, Per Day, Per Shift with the help of a precise Energy Monitoring system.
                10. This  can  be  achieved  in  steps  but  the  company  management  needs  to  make  proper
                    synchronization  of  Production>>Planning  &  Energy  /  Maintenance  Department  for  daily