                    discussions on Energy & Production. Deviations in SEC shall be discussed in daily meetings
                    and logical reasoning should be done.

                11. There is a need of monitoring the energy consumption throughout the year more closely
                    so  that  the  energy  consumption  can  be  matched  with  the  production  process  and
                    reduction of wastage of energy can be done during this time.

               The simple principle of Energy Conservation is

                   “MEASURE >> ANALYZE >> CONTROL >> SAVE >> SUSTAIN”


               Hence  a  Good  Monitoring  system  will  help  in  each  of  above  stage  and  will  give  the
               management a clear way for achieving the energy conservation.


                   1.  Periodic Energy Audits and consultation is very much necessary for implementing the
                       projects or developing the energy conservation mechanism as like TPM.
                   2.  This will be the streamlined approach towards Energy Conservation Standard ISO 50001.

               5.1  Major Energy Saving Opportunities in Electrical Section


                   a)  Our Study/Energy Audit is thus directed towards finding out the gaps in the operating
                       systems especially fixed costs energy centres i.e. Chillers, Cooling Towers, Illuminations,
                       Raw Water Pumping.

               Energy Saving Opportunities are divided into two segments for all utilities/equipment.


                  I.   Reduction in Specific Energy Consumption close to the design.
                 II.   Reduction  in wastage of energy through losses from  insulation,  in-effective practices,
                       design issues etc.
                       We have analyzed the data and further report is directed towards finding the reasons
                       for energy deviations and action plan thereafter.


                   b)  Average load on Transformer-1 is measured as 470 KW with a comparatively low power
                       factor of 0.83 and that of Transformer-2 is 298 KW with PF 0.82.
                   c)  Lower Power Factor results into higher demand and also system losses.
                   d)  As  per  measurements,  it  is  recommended  to  install  automatic  power  factor  control
                       panel of capacity 400 KVAR (at 440 V) for Transformer-1 & APFC panel of capacity 300
                       KVAR (At 440 Volts) for transformer-2. Since the system voltage is low, required capacity
                       is  slightly  increased.  This  is  necessary  from  DEWA  regulations  as  well.  Average

                       investment for the panels will be 65000 AED.
                   e)  The loads especially chillers, boiler  operate on very low power factor at no or partial
                       load.