                  7  KNX Powerline commissioning


                  7.1  Checking the local domain address (System ID)

                  Before a Powerline installation can be commissioned, the local interface should always be
                  checked for its domain address (System ID). The local interface must always have the
                  same domain address as assigned in the topology during the project design phase. The
                  domain address of the interface can be found under “Local interface settings”.













































                  Figure 18: Checking the local domain address (System ID)