KNX ADVANCED COURSE

                  End:  The telegram is received by 1-fold switch actuator 15.15.127 which then returns a
                        reply telegram (ACK).
                        The actuator then switches its output according to the transmitted value of the
                        communication object.


                  The result of using telegram filtering is that telegrams are only passed to lines that really
                  require them. Telegrams are not routed to places where they have no effect. The
                  advantage of this is that the bus load in the installation is reduced.

                  Line repeaters do not filter. They should therefore not be used in the planning of a new
                  KNX installation but in the extension of an existing one.

                  The routing counter has the benefit that even when the installation has faulty wiring (loop
                  formation with couplers), a telegram circulates in the loop a maximum of six times. The
                  installation is not blocked! On the other hand, the routing counter has the effect that a
                  telegram can only pass through a maximum of six couplers. As a result, line repeaters
                  may not be connected in series.

                  2.6  Telegram Structure for Download of couplers

                  For the download of filter tables, couplers are addressed by ETS with other telegram
                  types (APCIs) than normal devices.


                  2.7  Filter Table

                  The filter table is created automatically by ETS.

                  If a coupler is marked in the Topology View or the Building View, the contents of the filter
                  table can be displayed via context menu through the option Preview Filter Table....
                  The filter table which is actually present in the coupler is obtained via the menu item
                  Diagnostics/Device Info... of ETS3 Professional, if the box ‘group communication’ is
                  ticked in the then opening dialog box.
                  The filter table is edited in ETS3 Professional in the following way: The Topology window
                  and the Group Addresses window must be open. If group addresses are now dragged
                  onto a line via ‘drag & drop’, a new symbol is created in this line. It has the designation
                  “Manual Filter Table Entries”. If this symbol is selected, the manually entered group
                  addresses appear on the right hand side of the window.

                  Note:
                  If an entry should be deleted, the best method is to use the context menu. It is essential
                  to select ‘Remove’ and not ‘Delete’. ‘Delete’ would delete the group address completely
                  i.e. also from the group address table and in all places it was assigned.












                  Home and Building Management Systems                                   KNX Association
                  Couplers                             Couplers_E1209b.doc                           13/21