                  4.1  IP Router as Backbone Coupler
                  If an IP router is used as a backbone coupler with the physical address x.0.0 (e.g. 2.0.0),
                  no other IP routers may be used topologically “below” this IP router i.e. with a physical
                  address x.y.0 (y=1...15) (e.g. 2.1.0).




                                                         IP Network






                                      KNXnet/IP                                   KNXnet/IP
                                       Router                                      Router
                                        1.0.0                                       2.0.0
                                        4/1/1                                       4/1/1
                                                       Main Line 1                         Main Line 2

                       LC                LC               LC                 LC               LC
                       1.1.0            1.2.0            1.3.0              2.1.0            2.2.0
                     15/7/255           4/1/1            5/2/1                               4/1/1
                                        5/2/1

                            DVC              DVC               DVC                DVC              DVC
                            1.1.1            1.2.1             1.3.1              2.1.1            2.2.1
                            4/1/1            5/2/1             5/2/1              6/3/1            4/1/1


                            DVC              DVC               DVC                DVC              DVC
                            1.1.2            1.2.2             1.3.2              2.1.2            2.2.2
                                             4/1/1             5/2/1              6/3/1

                  Figure 5: IP router as backbone coupler