I N DUS T R I A L  A U T O M A TI O N  & P R O C E S S C O NTRO L C A B L E S                      126

        Technical Information




        UL Approved Insulation/Jacketing Options
                          UL Listed for MC and TC                      UL Listed for PLTC
                            Max. Temp Rating                   Insulation/Jacket  Max. Temp Rating
           Insulation/Jacket                  Flame Tests
                           Wet      Dry                       XLP/PVC             90°C
                                               UL 1685        XLP/CPE             90°C
         PVC-Nylon/PVC
            (THHN or THWN)   75°C   90°C        FT4/          PVC/PVC             105°C
            14 AWG & larger                  IEEE 1202/383
                                             ICEA T-29-520    PVC/CPE             105°C
                                               UL 1685        PE/PVC               75°C
         PVC-Nylon/PVC
            (TFN or TFFN)   75°C    90°C        FT4/          FPE/PVC              75°C
            16 & 18 AWG                      IEEE 1202/383
                                             ICEA T-29-520
                                                              XLP/Haloarrest      90°C
                                               UL 1685        FEP/FEP             200°C
         XLP/PVC or CPE                         FT4/
            (XHHW–2)       90°C     90°C     IEEE 1202/383
            14 AWG & larger                 VW-1 rated singles
                                             ICEA T-29-520
                                                                       Abbreviations Key
                                               UL 1685        CPE  Chlorinated Polyethylene
         XLP/PVC or CPE                         FT4/
            (RFH–2)        75°C     75°C     IEEE 1202/383    FEP  Fluorinated Ethylene-propylene
            16 & 18 AWG                     VW-1 rated singles
                                             ICEA T-29-520    FPE  Foam Polyethylene
         FRPO/PVC                                             FRPO  Flame-Retardant Polyolefin
            18 AWG & larger  —      75°C       UL  1685       PE   Polyethylene
         FRPO/PVC          75°C     90°C       UL 1685        PVC  Polyvinyl Chloride
         XLP/Haloarrest ®                      UL 1685             Nylon insulated singles are type THHN
            (XHHW-2)       90°C     90°C    FT4/IEEE 1202/383      or THWN for conductors 14 AWG or larger.
            14 AWG & larger                  ICEA T-29-520         Conductor sizes 16 and 18 AWG are
                                                                   Type TFN or TFFN singles.
         XLP/Haloarrest                        UL 1685
            (RFH-2)        75°C     75°C    FT4/IEEE 1202/383   XLP  Cross-Linked Poly
            16 & 18 AWG                      ICEA T-29-520         Cross-Linked Poly (XLP) insulated singles
                                                                   are type XHHW-2 for conductors 14 AWG
         XLP/HaloarrestXLink ™ -1              UL 1685             or larger. Conductor sizes 16 and 18 AWG
            (XHHW-2)       90°C     90°C    FT4/IEEE 1202/383      are RFH-2.
            18 AWG & larger                 VW-1 rated singles
         XLP/HaloarrestXLink-2                 UL 1685
            (XHHW-2)       90°C     90°C    FT4/IEEE 1202/383
            18 AWG & larger                 VW-1 rated singles
         FEP/PVC           90°C     90°C       UL 1685
        Vertical Tray Flame Test Comparison
                                             FT4/IEEE 1202/
              Test         UL 1685 (UL 1581)                  IEEE 383-1974      IEC 323-3      ICEA T-29-520
                                             IEEE 383-2003
         Flame Test Chamber  Vertical Tray  Vertical Tray  Vertical Tray    Vertical Tray    Vertical Tray
         Burner Type    Ribbon gas burner  Ribbon gas burner  Ribbon gas burner  Ribbon gas burner  Ribbon gas burner
         Theoretical Heat Input  70,000 BTU/hr  70,000 BTU/hr  70,000 BTU/hr  70,000 BTU/hr  210,000 BTU/hr
         Burner Positioning  horizontal 3" from samples   20° up from horizontal    horizontal 3" from samples   horizontal 2.95" from cable   horizontal 8-1/4" from
                        18” from tray base  2.95" from cable surface   18" above tray bottom  surface 23.6" above floor  cable surface 12-1/4"
                                         11.8" above floor                                   above tray base
         Tray Dimensions  8' length, 12" width,    9.84' length, 11.81" width,   8' length, 12" width,    11.5' length, 19.7" width,   8' length, 12" width,
                        3" side flanges  2.85" side flanges  3" side flanges  side flanges: none  3" side flanges
         Sample Spacing  1/2 cable diameter  1/2 cable diameter  1/2 cable diameter  lesser of 1/2 cable diameter   1/2 cable diameter
                                                                            and .78"
         Duration of    20 minutes       20 minutes       20 minutes        20 minutes       20 minutes
         Flame Application
         Mode of Failure  Cable blistering or charring   Cable char has exceeded    Cable blistering or charring   Cable charring has reached   Cable blistering or charring
                        has reached the top of the   a length of 4.92'.  has reached the top of the   a height of 98.4" above the   has reached the top of the
                        sample after the cable has        sample after the cable has   bottom of the burner.  sample after the cable has
                        self-extinguished.                self-extinguished.                 self-extinguished.