Page 213 - belden
P. 213

PA I R E D  C A B L E S                                                                            213

               Audio, Control and Instrumentation Cables




               Individually Shielded Pairs • RS-485








                                                    Insulation    Jacket           Capacitance
                             Color     OD (Nom)     Thickness   Thickness
                Part No.  Pairs                                             Cond. - Cond.  Cond. - Shield  Additional Features/Ratings
                             Code
                                     Inch   mm    Inch   mm    Inch  mm    pF/Ft  pF/m  pF/Ft  pF/m
               22 AWG • FEP/Flamarrest  ®
                 Stranded (7 x 30) TC Conductors • FEP Insulation • Individually Beldfoil ®  Shielded Pairs • 24 AWG TC Drain Wire • Natural Flamarrest Jacket. Pairs Cabled on a Common Axis
                 to Reduce Diameter.
                                                                                                      Plenum • Non-Conduit
                                                                                                     NEC: CMP • CEC: CMP FT6
                                                                                                          300V
                            Black-Red
                 82723  2             .153  3.89  .007   .18   .017  .43    43    141    75    246    45 Ω Nom. Impedance
                           Green-White
                                                                                                      66%Velocity of Prop.
                                                                                                    Conductor DCR (Nom): 14.7 Ω
                                                                                                       /1000’ (48.2 Ω/km)
               22 AWG • FEP/FEP
                 Stranded (7 x 30) TC Conductors • FEP Insulation • Individually Beldfoil Shielded Pairs • 24 AWG TC Drain Wire • Red FEP Jacket. Pairs Cabled on a Common Axis
                 to Reduce Diameter.
                                                                                                      Plenum • Non-Conduit
                                                                                                     NEC: CMP • CEC: CMP FT6
                                                                                                          300V
                            Black-Red
                 88723  2             .148  3.76  .007   .18   .014  .36    35    115    67    220    45 Ω Nom. Impedance
                           Green-White
                                                                                                      66%Velocity of Prop.
                                                                                                    Conductor DCR (Nom): 14.7 Ω
                                                                                                       /1000’ (48.2 Ω/km)
               22 AWG • FEP/Fluorocopolymer
                 Stranded (7 x 30) TC Conductors • FEP Insulation • Individually Beldfoil Shielded Pairs • 24 AWG TC Drain Wire • Red Fluorocopolymer Jacket. Pairs Cabled on a Common Axis
                 to Reduce Diameter.
                                                                                                      Plenum • Non-Conduit
                                                                                                     NEC: CMP • CEC: CMP FT6
                                                                                                          300V
                            Black-Red                                                                                     Paired Cable
                 87723  2             .148  3.76  .007   .18   .014  .36    35    115    67    220    45 Ω Nom. Impedance
                           Green-White
                                                                                                      66%Velocity of Prop.
                                                                                                    Conductor DCR (Nom): 14.7 Ω
                                                                                                       /1000’ (48.2 Ω/km)



























               TC = Tinned Copper• FEP = Fluorinated Ethylene Propylene

                                   Fo r  m o r e  i n fo r m at i o n,  c o n t a c t   Be ld e n  Te ch n i ca l  S u ppo r t :   1- 8 0 0 - B E L D E N -1  •  www. b e l d e n . c o m
   208   209   210   211   212   213   214   215   216   217   218