Page 542 - APPLIED PROCESS DESIGN FOR CHEMICAL AND PETROCHEMICAL PLANTS, Volume 1, 3rd Edition
P. 542

508                       Applied  Process Design for Chemical  and  Petrochemical  Plants


              For vent area  limited  or  restricted  to  one  end  of an   From Table 7-27:
           elongated enclosure  (vertical  tank,  silo, etc.), the venting
           equation is limited to:                                      C  =  0.17  (psi)  i/s

                                                                      Pred  =  0.40  =  0.40 psi
                                                         (7-68)
                                                                                           1
                                                                       A,.= 0.17 (16,000)/(0.40) 1 2  = 4,300 sq ft
           where  L3  =  longest dimension of the enclosure, ft
                  A  =  cross section area, sq ft                   This will  require  roof bursting panels,  side  wall  burst-
                 Per  =  perimeter of cross section,  ft         ing panel,  or an end panel  that could be  hinged to  blow
                                                                 out.  The  panel  relieving  pressure  should  be  set for 0.40
              For  highly  turbulent gas  mixing  in  an  enclosure  and   psi  - 0.35  psi  =  0.05  psi  to burst or relieve  per code.
            the  vent  area  is  restricted  to  one  end  of the  elongated
            enclosure,  ratio of length-to-diameter should not exceed   High Strength Enclosures for Deflagrations
            2,or

                                                                    This  section  and  Chapters  6  and  7  of the  code  [27)
                                                         (7-69)
                                                                 apply  to  vessels  and  equipment capable  of withstanding
                                                                 more  than  1.5  psig  internal  pressure.  These  design  pro-
              For other conditions,  refer to  the  NFPA-68  Code.  For
            the  above  relations  to  apply,  the  constant,  C,  should  be   cedures do not apply  to a detonation  that is not believed
            referred to fuels having the characteristics of one of those   to be capable of being vented successfully  [27).
            in Table 7-27.                                          The vent devices used to relieve the overpressure from
              Ref.  [27)  presents  a  thorough  discussion  of limits  to   the  deflagration  must  be  structurally  sound,  low  in
            structural  components  strengths,  and  these  should  be   weight,  and  should  not fragment to  form  missiles  when
            observed.  Ductile  design  practices  should  be  used.  The   the force hits the device.
            maximum allowable design stress should not exceed 25%   The discharge from high pressure vessels must be vent-
            of the  ultimate  strength.  The  strength  of the  enclosure   ed out of the  building  to  avoid fires  and explosions  and
            should exceed the vent relief pressure by at least 0.35 psi.   overpressure  in  the  building,  and  the  backpressure  or
              The vent design must provide at least the area required   pressure  loss  through  the vent duct/pipe  must be  recog-
            to satisfy  the volume of the enclosure  (see NFPA-68)  [27).   nized  as  affecting  the  relieving  pressure  of  the  vessel.
                                                                 Never locate  a vent duct discharge  to  atmosphere  in  an
            Example 7-17: Low Strength Enclosure Venting         area where  the  discharge  might be  drawn  into  (a)  fresh
                                                                 air intake  to  a  building  or,  (b)  fresh air intake  to a com-
              Design  to protect a large warehouse containing plastic   pressor or gas fired engine.
            materials  that  can  emit  ethylene  and  propylene  vapors.   Rupture  disks when  properly sized and located on  the
            The  dimensions  on  the  rectangular  building  with  a  flat   potentially  overpressure  vessel  have  been  shown  to  pro-
            roof are:                                            vide the best protection for a deflagration but not a deto-
                                                                 nation  [54).
              100 ft long  X  50 ft wide  X  20 ft tall.
                                                                 Determination of Relief Areas for Deflagrations  of
              The building design  has been selected as good for 0.4
            psi overpressure.  See Table 7-23 for glass window shatter-   Gases/Vapors/Mists in High Strength Enclosures
            ing.  Use known  design figures when available.
              Areas are:                                            The  nomographs  of Figures  7-63  A,  B,  C,  and D  [27)
                                                                 were developed by Bartknecht [54)  for the conditions of:
                 Floor =  100  X  50   5,000 sq ft
                 Roof= same           5,000 sq ft                   • no turbulence in vessel  at time of ignition
                 2  ends  =  2  X  50  x  20   2,000 sq ft          • low  ignition energy of 10 joules or less
                 2 sides  = 2  X  100  x  20  =  4,000 sq ft
                                      16,000 sq ft                  •  atmosphere pressure

              Vent area:                                            To  utilize  the  charts  Figures  7-63A  thru  D,  enter vol-
                                                                 ume,  read  up  to  selected  Prcd  value  and  across  to  vent
                                                         (7-67)   pressure P,ta,,  and down to vent area required.
   537   538   539   540   541   542   543   544   545   546   547